ELE08-00142
| ELE-Aging Inspection | 9/16/2009 | 9/16/2009 | 9/18/2009 3:54:27 PM | | DONE |
|
|
no activity, suc
|
ELE09-01741
| Electrical Rough-In | 9/16/2009 | 9/16/2009 | 9/17/2009 8:06:54 AM | P | CANC |
|
|
jared ###-#### see response to inspection 9-17-09
|
ELE08-01472
| ELE-Aging Inspection | 9/16/2009 | 9/16/2009 | 9/16/2009 4:37:17 PM | | DONE |
|
|
no activity, waiting for contractor to call, suc
|
ESC09-00332
| General Inspection | 9/16/2009 | 9/16/2009 | 9/16/2009 4:01:02 PM | P | PASS |
|
|
looked ok
|
ELE09-01103
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 3:42:41 PM | P | PASS |
|
|
CONTACT: NEIL RAMSEY Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to final, signed occupancy card, no esc this project
|
ELE09-01482
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 3:23:26 PM | P | PASS |
|
|
darel ###-#### corrections made, ok to final
|
ELE09-01102
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 3:13:57 PM | P | PASS |
|
|
CONTACT: NEIL RAMSEY Phone #: ###-#### Internet Inspection Request from: Deb Gooden ok to final, signed occupancy card, no esc this project
|
ELE09-01570
| Permanent Service | 9/16/2009 | 9/16/2009 | 9/16/2009 2:30:15 PM | P | PASS |
|
|
Rocky-please call 30 mins prior to inspection Phone #: ###-#### p/s o/h rec ok, no esc this project
|
ELE09-01570
| Electrical Rough-In | 9/16/2009 | 9/16/2009 | 9/16/2009 2:29:58 PM | P | PART |
|
|
Rocky-please call 30 mins prior to inspection Phone #: ###-#### front room opened up without plaster ok to cover, most of rest is cut-in, can see more like in basement at final, no esc this project
|
ELE09-01354
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 1:28:45 PM | P | FAIL |
|
|
Jared-please call at least 30 mins prior for access Phone #: ###-#### caled, left correction notice, NEC 110.3(B) listed equipment shall be installed per instructions, 110.22(A) each disconnect shall be legibly labelled and suitable for environment, 406.4 receptacles shall be securely mounted
|
ELE09-01205
| Final | 9/15/2009 | 9/16/2009 | 9/16/2009 10:40:01 AM | A | PASS |
|
|
Please provide final inspection. Phone #: ###-#### Internet Inspection Request from: Spencer Mclean ok to final, no esc this project
|
ESC07-00781
| Site Final | 9/16/2009 | 9/16/2009 | 9/16/2009 9:56:56 AM | A | PASS |
|
|
site ok, ok to final
|
ELE09-01684
| Final | 9/16/2009 | 9/16/2009 | 9/16/2009 9:49:25 AM | A | PASS |
|
|
this is a final for the fuel canopy,thanks.Contact will be Drew ###-#### Internet Inspection Request from: Laura Longshaw ok to final, signed card, no esc this project
|
ELE09-00946
| Final | 9/15/2009 | 9/16/2009 | 9/16/2009 9:27:43 AM | A | PASS |
|
|
This inspection will be for a final please. Contact is Rey. Thank you and have a super day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw ok to final, signed occupancy card, no esc this project
|