FIR05-00021
| FIR-Aging Inspection | 9/16/2010 | 9/16/2010 | 9/23/2010 11:01:32 AM | | DONE |
|
|
I spoke to Nick with Taylor Brothers. He is going to get them scheduled.
|
FIR04-00523
| FIR-Aging Inspection | 9/16/2010 | 9/16/2010 | 9/21/2010 2:19:48 PM | | NR |
|
|
Per Rod Walters with Simplex this permit will be voided.
|
BLD10-00636
| FIRE-Final Inspection | 9/16/2010 | 9/16/2010 | 9/16/2010 4:17:07 PM | P | PASS |
|
|
life safety passed
|
BLD10-01995
| FIRE-Conference | 9/16/2010 | 9/16/2010 | 9/16/2010 4:15:56 PM | P | DONE |
|
|
I went over life safety requirements with Noah which included door hardware, fire extinguishers and requirements for the medical gas closet which could include fire sprinklers. Noah needs to provide additional information the gas type stored and quantity.
|
BLD10-01746
| FIRE-Final Inspection | 9/16/2010 | 9/16/2010 | 9/16/2010 4:11:29 PM | P | PASS |
|
|
Life safety passed.
|
FIR10-00459
| INSP-Final Inspection | 9/16/2010 | 9/16/2010 | 9/16/2010 3:08:40 PM | P | PASS |
|
|
Permit finaled
|
MIS10-00268
| FIR-Conference | 9/15/2010 | 9/16/2010 | 9/16/2010 3:06:20 PM | A | DONE |
|
|
This is a partial inspection only. A full inspection can be completed when building plans have been issued. Additioal corrections may be required. 1 provide recertification of the kitchen hood fire suppression system or permit if modifications are required, 2 provide all required fire extinguishers with current inspection tags mounted in a normal path of travel, 3 repair/provide exit signs and emergency lighting, 4 provide single action hardware on the rear kitchen exit door and remove the dead bolt, 5 provide sticker "Door to remain unlocked while building is occupied" at the main exit with the keyed hardware, 6 provide building address on both street sides of the building with atleast 4" high numbers of a contrasting color, 7 provide current occupant load signage.
|
BLD09-02238
| FIRE-Final Inspection | 9/15/2010 | 9/16/2010 | 9/16/2010 1:38:39 PM | A | FAIL |
|
|
The main exit shall comply with IFC 1008.1.3.4 for access controlled egress doors, this includes fire alarm tie in and request to exit button. Single action hardware can be provided or keyed hardware with indicator. Repair the exit sign in the large breakroom and provide single action hardware on the exterior exit door from the large breakroom.
|
BLD10-02147
| FIRE-Final Inspection | 9/14/2010 | 9/16/2010 | 9/16/2010 1:07:56 PM | A | FAIL |
|
|
Provide passing final inspection for the building related fire alarm permit for the installation of th AES panel. Remove the thumbturn deadbolt from the main exit. Keyed is ok. Meet with Perry for the revised floor plan.
|
BLD10-02105
| FIRE-Final Inspection | 9/15/2010 | 9/16/2010 | 9/16/2010 10:43:02 AM | A | PASS |
|
|
Life safety passed.
|
FIR09-00083
| INSP-Final Inspection | 9/15/2010 | 9/16/2010 | 9/16/2010 10:42:02 AM | A | PASS |
|
|
Permit finaled. The netcon was a 5
|