Inspections for the day of: Friday, September 16, 2011.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD10-01664 FIRE-Final Inspection9/16/20119/16/20119/16/2011 4:52:06 PMPPASS
Previously noted correction items verified for completion. Fire life safety finaled.
BLD11-02144 FIRE-Final Inspection9/16/20119/16/20119/16/2011 4:50:53 PMPFAIL
Remove conflicting address numbers, provide approved hardware at the secondary exit door (keyed hardware allowed at only one location).
FIR11-00413 INSP-Final Inspection9/16/20119/16/20119/16/2011 4:48:24 PMPPART
Relocated heads at marked locations with today's date on approved plans okay for cover.
FIR11-00221 INSP-Final Inspection9/16/20119/16/20119/16/2011 4:46:37 PMPPASS
Correction items completed. Final walkthrough passed, permit finaled.
FIR11-00355 INSP-Sprinkler Rough-in9/16/20119/16/20119/16/2011 4:45:34 PMPFAIL
Inspection for cover at the three 2nd floor classrooms and both the 1st floor restrooms failed due to obstructed heads, one missing head, missing seismic bracing, sprig in need of adjustment, access, etc.
BLD11-02237 FIRE-Final Inspection9/15/20119/16/20119/16/2011 11:05:46 AMAPASS
Fire life safety inspection completed satisfactory.