Inspections for the day of: Tuesday, September 16, 2014.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MIS14-00210 ELE-Conference9/15/20149/16/20149/16/2014 3:19:34 PMPDONE
substandard renters complaint // Chuck ###-#### Section 4-05-18 ELECTRICAL PERMIT REQUIRED
Before any person installs or alters any electrical wiring, equipment, apparatus or fixture, they
shall file a permit application with the Electrical Section. In past 10-3 NM cable enters panel with out abrasion protection, illegally taps off main lugs of panel so wire protected by main fuses only. Wire runs under trailer which is concidered damp location, NM cable not approved for damp location.
Issues noted on complaint serious maintainence needed.
ELE13-00365 Electrical Rough-In9/16/20149/16/20149/16/2014 2:54:11 PMPPASS
Bater Phone #: ###-#### Small shed single circuit feeder, large shed more than 2 circuits 60 amp feed minimum will check next trip. Large shed not habitable room, hobby room/ work shop. Wall and ceiling rough in ok cover.
ELE14-01775 Electrical Rough-In9/16/20149/16/20149/16/2014 1:23:56 PMPPASS
Daryl- library clouds Phone #: ###-#### Library clouds rough in ok to hang. Fixtures to be supported independant of cloud support system
ELE14-01471 Final9/15/20149/16/20149/16/2014 11:07:22 AMAFAIL
call corey with questions Phone #: ###-#### Inspection requested via web by Don Lustig
406.9 Receptacles in Damp or Wet Locations. All
15- and 20-ampere, 125- and 250-volt nonlocking receptacles
shall be a listed weather-resistant type.
ELE14-01848 Electrical Rough-In9/15/20149/16/20149/16/2014 10:18:38 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid rough in ok cover
GCE14-00054 GCE-Final9/15/20149/16/20149/16/2014 9:44:43 AMAPART
Mike ###-#### 110.22 Identification of Disconnecting Means.
(A) General. Each disconnecting means shall be legibly
marked to indicate its purpose unless located and arranged
so the purpose is evident. The marking shall be of sufficient
durability to withstand the environment involved.
Install utilty bond bar.
Install or blank off front light boxes
Temp occupancy ok
ELE14-02576 Rough-In Permanent Service9/15/20149/16/20149/16/2014 8:45:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Neal Rumsey Rough in ok cover p/s u/g n ok