Inspections for the day of: Friday, September 16, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Story
TitleELE-INSPECTOR
Phone #985-3493
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-01348 Electrical Rough-In9/16/20169/16/20169/16/2016 2:52:21 PMPPASS
overhead Level 1 stack 2 partial. Call Frank. Requesting after 2 pm show up. Phone #: ###-#### Inspection requested via web by Brandon Robinson

hard lid as noted on print ok to cover
ELE16-00089 Electrical Rough-In9/15/20169/16/20169/16/2016 2:30:00 PMPPASS
. Call Rafael for inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo

2nd floor area grid as noted on print
ELE16-00089 Final9/16/20169/16/20169/16/2016 2:27:45 PMPPART
TCO inspection for 4th and 5th floor of GBAD buidling TI portion. Call Rafael for inspection. Phone #: ###-#### Inspection requested via web by Rafael Castillo

4th floor only ok to occupy...5th floor fail for 2 outlets and bonding of cable tray
ELE15-00495 Final9/16/20169/16/20169/16/2016 2:24:31 PMPFAIL
Walk 5 story for TCO. Contact is Toby Groves ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves

exit signs need installed x 2
ELE16-00198 Electrical Rough-In9/15/20169/16/20169/16/2016 12:44:11 PMPFAIL
Juanita Phone #: ###-####

334.30 romex shall be supported within 12" of box

300.4(b) conductor larger than #4 shall have bushing

all openings shall be closed-sub panel

conference needed
ELE16-03007 Rough-In Permanent Service9/16/20169/16/20169/16/2016 12:27:53 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov

roughin ok to cover
p/s u/g n ok 5 meters
ELE16-00506 Final9/15/20169/16/20169/16/2016 11:25:24 AMACANC
closing off the electrical
waiting for inspections to be moved to proper permit
ELE16-01750 Final9/13/20169/16/20169/16/2016 10:03:04 AMAFAIL
Robert. Temp occupancy. Phone #: ###-#### Inspection requested via web by Sean DeLacy

not ready...missing plates, lights, gfi protection...whips for heaters and equipment not installed...gfi breakers need installed for employee areas
ELE15-01348 Electrical Rough-In9/15/20169/16/20169/16/2016 9:34:31 AMAPASS
Quad Core Elev. Pits ; top of hoistway east side Ground Level stack 1

Conference on Article 400.7 and 400.8 IDF Rack PWR
Walk thru Basement Discuss TCO prior to meeting 9/21
Thanks
Phone #: ###-#### Inspection requested via web by Tom Betty

rough elevator pit and hoist area-light and outlet ok....conference wiring of low volt room using s/o cable for wiring method....tco conference did not do-wait for Rock/Daryl
ELE16-03006 Temporary Service9/15/20169/16/20169/16/2016 8:22:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton

t/s u/g n ok