Inspections for the day of: Friday, September 16, 2016.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00360 INSP-Final Inspection9/15/20169/16/20169/16/2016 3:02:16 PMPFAIL
Provide updated map at the FACP showing the location and device count of the new portable, provide transient protection per NFPA 72 12.2.4.2 and NFPA 70 article 760, provide as-builts to plan review showing the communication method (alarm/trouble circuit) to the existing Simplex panel in the main school building. Include data sheet for suppression method.
BLD16-01523 FIRE-Final Inspection9/16/20169/16/20169/16/2016 1:04:45 PMPPASS
Life safety passed. it appears the existing fire alarm notification dvices are spaced adequately for the new walls.
BLD16-03315 FIRE-Final Inspection9/15/20169/16/20169/16/2016 1:03:22 PMPFAIL
Replace the expired exit signs and provide/repair emergency lights as discussed.
BLD16-02709 FIRE-Final Inspection9/16/20169/16/20169/16/2016 10:29:51 AMAPASS
life safety passed
BLD16-01225 FIRE-Final Inspection9/15/20169/16/20169/16/2016 10:29:34 AMAPART
A temporary occupancy is given for life safety with scott's permission until the occupant load sign and the exit discharge lights have been installed
BLD16-02335 FIRE-Final Inspection9/15/20169/16/20169/16/2016 9:10:06 AMAPASS
life safety passed
BLD16-02006 FIRE-Final Inspection9/16/20169/16/20169/16/2016 8:20:05 AMPPASS
Life safety passed
FIR16-00530 INSP-Final Inspection9/15/20169/16/20169/16/2016 8:19:47 AMAPASS
Permit finaled
FIR16-00533 INSP-Final Inspection9/14/20169/16/20169/16/2016 8:19:28 AMAPASS
Permit finaled