NAF16-00055
| INSP-Sprinkler Rough-in | 9/16/2016 | 9/16/2016 | 9/16/2016 1:50:46 PM | P | FAIL |
|
|
From stub up to ~15' from building. Minimum ground coverage (4'-6") not acheived. Pipe has approx. 3'-6". Not approved for cover.
|
NAF15-00041
| INSP-Sprinkler Rough-in/Hydro | 9/15/2016 | 9/16/2016 | 9/16/2016 12:57:47 PM | A | PASS |
|
|
Underground hydro completed satisfactory
|