Inspections for the day of: Friday, September 16, 2016.
Number of inspections: 2
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
NAF16-00055 INSP-Sprinkler Rough-in9/16/20169/16/20169/16/2016 1:50:46 PMPFAIL
From stub up to ~15' from building. Minimum ground coverage (4'-6") not acheived. Pipe has approx. 3'-6". Not approved for cover.
NAF15-00041 INSP-Sprinkler Rough-in/Hydro9/15/20169/16/20169/16/2016 12:57:47 PMAPASS
Underground hydro completed satisfactory