Inspections for the day of: Friday, September 16, 2016.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00727 INSP-Sprinkler Rough-in/Hydro9/16/20169/16/20169/16/2016 4:32:09 PMPPASS
Hydrostatic test complete for wet pipe? fire sprinkler systems located on levels 2 and 4 (Area labeled level 5 is off of the level 4 wet system) Standpipe hydrostatic test for district/convention center complete.
FIR15-00727 INSP-Sprinkler Rough-in9/9/20169/16/20169/16/2016 4:27:28 PMPPASS
24 hour air test complete for level 2 and level 3 dry systems protecting parking garages. 200psi hydrostatic test complete for parking garage dry systems (level 2 and 3)
FIR15-00751 INSP-Final Inspection9/16/20169/16/20169/16/2016 4:25:34 PMPPART
Partial final fire alarm inspection for the district side of the convention center complete. Items still needing to be inspected is the kitchen area of level 1. Area labeled as level 5, level 4 , level 3 parking, level 2 parking, level 2 and level 1 lobby area complete for audio/visual notification on fire alarm system.
FIR16-00265 INSP-Sprinkler Rough-in/Hydro9/13/20169/16/20169/16/2016 4:19:34 PMPPASS
Rough to cover inspection complete for overhead fire sprinkler piping located in VRT, overhead fire sprinkler piping located in VRT approved for cover.
FIR16-00420 INSP-Final Inspection9/16/20169/16/20169/16/2016 9:56:01 AMAPASS
Final fire alarm inspection passed/complete.
FIR16-00311 INSP-Final Inspection9/16/20169/16/20169/16/2016 9:53:58 AMAPASS
Final fire sprinkler inspection passed/complete.
FIR16-00424 INSP-Sprinkler Rough-in9/15/20169/16/20169/16/2016 9:51:59 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping complete, overhead fire sprinkler piping approved for cover per this area of work.
FIR15-00602 INSP-Sprinkler Rough-in/Hydro9/15/20169/16/20169/16/2016 8:54:53 AMACANC
Hydrostatic test cancelled per conversation with point of contact, Jeff ###-####. Hydrostatic test will be rescheduled after system will hold test.