Inspections for the day of: Monday, September 16, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03397 Final9/15/20199/16/20199/16/2019 3:22:44 PMPPASS
please call half hour ahead Tamera ###-#### code south door 6066# Phone #: ###-#### Inspection requested via web by Barbara Szurgot
No changes to walls, just refinishing, all wiring associated items noted fished in. Final ok
ELE19-00602 Electrical Rough-In9/16/20199/16/20199/16/2019 3:00:14 PMPPASS
Garage stairwell. Danny is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Levels 3 to 4 South East stair wall rough in ok cover
ELE19-00601 Electrical Rough-In9/16/20199/16/20199/16/2019 2:58:55 PMPPASS
Podium deck hotel side. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Area noted over pool. pour noted rough in ok cover.
ELE19-03174 Conference9/16/20199/16/20199/16/2019 2:12:41 PMPDONE
Phone #: ###-#### Inspection requested via web by Jeremy Cloud
Discussed if a GFCI device is allowed behind an appliance with wheels. If appliance is easily moved GFCI device is ok behind appliance.
Also width of work space required for a panel board. As per 110.26(A)(2) a minimum of 30" or width of equipment is required. Lighting control panel mounted of left wall does not affect work space width of panel in question.
ELE19-03479 Electrical Rough-In9/16/20199/16/20199/16/2019 1:30:13 PMPPASS
listing inspection for solar equipment

Please call the installer on your way out - We want to make sure we are there ya!!

Call Logan 208.761.4280
We are doing service calls all day and won''t go to that site to finish the install until you''ve seen it.

Thanks guys Phone #: ###-#### Inspection requested via web by Ryan King
20 amp over current required per drawing. listing confirmed. Rough in ok
ELE19-03348 Final9/13/20199/16/20199/16/2019 10:14:34 AMAFAIL
Phone #: ###-#### Inspection requested via web by Kevin Perez
422.31- A disconnecting means shall be provided for all appliances. 110.25 lockouts acceptable. Brkr 32 right panel.
ELE19-03424 Rough-In Permanent Service9/13/20199/16/20199/16/2019 9:32:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Tyler Ridley
Service only.... p/s o/h n ok
ELE19-02836 Permanent Service9/13/20199/16/20199/16/2019 9:08:42 AMAPASS
Phone #: ###-#### Inspection requested via web by Angela Stears p/s u/g rec ok
ELE19-02836 Electrical Rough-In9/16/20199/16/20199/16/2019 9:08:20 AMPFAIL
Phone #: ###-#### Inspection requested via web by Angela Stears
300.5- Underground from pedistal to under mobile home shall be 18" deep to top of conduit minimum.
Chasis bond complete.
ELE19-03475 Temporary Service9/15/20199/16/20199/16/2019 9:01:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Dylan Pierce t/s u/g n ok
ELE19-02529 Final9/13/20199/16/20199/16/2019 8:22:32 AMAPASS
Replace two wall signs with new signs reading Extra Mile. All Primary power to remain as is. Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok