Inspections for the day of: Tuesday, September 17, 2002.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02639 Electrical Rough-In9/16/20029/17/20029/17/2002 12:00:00 AMAPART
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung conduit in pour ok 9/17/2002 10:47:25 AM
ELE02-00309 Final9/16/20029/17/20029/17/2002 12:00:00 AMAFAIL
###-#### cor. and do not cover posted called left message250.148, and 250.8 grd light fixtures with approved screws or clips, 250.104(C) bond building using a lug ,not a nutand bolt with 2 washers, 210.70 needs switch and light for back door of shop, 300.14 cut wires too short at boxes, 334.30 secure romex within 8 inches of plastic boxes and 12 inches where boxes have romex connectors 9/17/2002 11:21:59 AM
ELE02-02228 Final9/16/20029/17/20029/17/2002 12:00:00 AMACANC
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
ELE02-02872 Final9/16/20029/17/20029/17/2002 12:00:00 AMPPASS
###-#### SPA ok 9/17/2002 2:27:50 PM
ELE02-02836 Rough-In Permanent Service9/17/20029/17/20029/17/2002 12:00:00 AMPPASS
###-#### r/i ok



p/s u/g new ok 9/17/2002 12:05:10 PM
ELE02-02802 Final9/17/20029/17/20029/17/2002 12:00:00 AMPPASS
phil ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 9/17/2002 2:58:02 PM