ELE02-02639
| Electrical Rough-In | 9/16/2002 | 9/17/2002 | 9/17/2002 12:00:00 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung conduit in pour ok 9/17/2002 10:47:25 AM
|
ELE02-00309
| Final | 9/16/2002 | 9/17/2002 | 9/17/2002 12:00:00 AM | A | FAIL |
|
|
###-#### cor. and do not cover posted called left message250.148, and 250.8 grd light fixtures with approved screws or clips, 250.104(C) bond building using a lug ,not a nutand bolt with 2 washers, 210.70 needs switch and light for back door of shop, 300.14 cut wires too short at boxes, 334.30 secure romex within 8 inches of plastic boxes and 12 inches where boxes have romex connectors 9/17/2002 11:21:59 AM
|
ELE02-02228
| Final | 9/16/2002 | 9/17/2002 | 9/17/2002 12:00:00 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
ELE02-02872
| Final | 9/16/2002 | 9/17/2002 | 9/17/2002 12:00:00 AM | P | PASS |
|
|
###-#### SPA ok 9/17/2002 2:27:50 PM
|
ELE02-02836
| Rough-In Permanent Service | 9/17/2002 | 9/17/2002 | 9/17/2002 12:00:00 AM | P | PASS |
|
|
###-#### r/i ok
p/s u/g new ok 9/17/2002 12:05:10 PM
|
ELE02-02802
| Final | 9/17/2002 | 9/17/2002 | 9/17/2002 12:00:00 AM | P | PASS |
|
|
phil ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 9/17/2002 2:58:02 PM
|