FIR03-00337
| INSP-Final Inspection | 9/16/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 10:33:05 AM. Contact: ###-####. need updated map and NFPA 72 forms 9/17/2003 5:58:53 PM
|
FIR03-00462
| INSP-Sprinkler Rough-in/Hydro | 9/16/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 1:48:45 PM. Contact: ###-####. heads installed in soffits that are 12 inches - heads to be within 1-4 inches of ceiling and will require heads in pockets with calc's; need to verify 2 inch water meter; tenting not completed; minor changes made to piping including location of pipe to second floor; spare head box and test alarms; there is a control valve below backflow that is not allowed and can be relocated to shut off domestic 9/17/2003 2:24:37 PM
|
BLD00-03496
| FIRE-Final Inspection | 9/16/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | A | PASS |
|
|
sid , ###-#### call prior to inspection///MWL
|
BLD03-01635
| FIRE-Final Inspection | 9/16/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 3:20:12 PM. Contact: ###-####.
|
BLD03-01635
| FIRE-Alarm Testing | 9/16/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 3:21:11 PM. Contact: ###-####.
|
BLD03-01635
| FIRE-Sprinkler Rough-in | 9/16/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 9/16/2003 at 3:22:59 PM. Contact: ###-####.
|
FIR03-00533
| INSP-Final Inspection | 9/17/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | CANC |
|
|
mike; Phone #: ###-#### Internet Inspection Request from: Marc Lileks
|
FIR03-00141
| INSP-Final Inspection | 9/17/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | PASS |
|
|
|
BLD02-02863
| FIRE-Final Inspection | 9/17/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | PASS |
|
|
|
BLD03-00334
| FIRE-Final Inspection | 9/17/2003 | 9/17/2003 | 9/17/2003 12:00:00 AM | P | FAIL |
|
|
door hardware on meeting room door; canopies on fire sprinklers; laundry room door closure and smoke seal; exit signs and emergency lights okay
|