Inspections for the day of: Monday, September 17, 2007.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00251 FIR-Aging Inspection9/17/20079/17/20079/17/2007 4:49:47 PM DEFR
Work in progress.
FIR07-00753 INSP-Final Inspection9/14/20079/17/20079/17/2007 4:46:52 PMPPASS
Fire alarm testing passed, noted the duct dectector has been deleted due to cfm below min. required, permit finaled.
FIR07-00571 INSP-Final Inspection9/17/20079/17/20079/17/2007 4:45:13 PMPNR
Missing escutcheons, noted two rooms lacking required fire sprinkler coverage within the tenant remodel area.
FIR07-00446 INSP-Sprinkler Rough-in/Hydro9/14/20079/17/20079/17/2007 4:42:18 PMAPART
Overhead hydrostatic test for the two wet systems and the antifreeze loop passed, remainder of OH install is complete and corrections made, noted one pendent head to be changed to a 155 deg as discussed.
FIR07-00623 INSP-Sprinkler Rough-in9/17/20079/17/20079/17/2007 4:39:15 PMAPART
OH rough-in is approved for cover, noted field changes are acceptable, final pending ceiling tile and escutcheons.
FIR07-00154 INSP-Final Inspection9/14/20079/17/20079/17/2007 4:33:46 PMAPASS
Fire sprinkler permit work completed satisfactory, permit finaled.
FIR07-00617 INSP-Final Inspection9/14/20079/17/20079/17/2007 11:48:22 AMAFAIL
The duct detector vent tubes are not installed correctly.
BLD07-00908 FIRE-Final Inspection9/14/20079/17/20079/17/2007 11:46:57 AMAFAIL
Missing approved door hardware at the second floor stairway exit and office doors, need to install two exit signs at the 2nd floor as red-lined per plan review, missing a fire sprinkler head in a utility closet on the second floor, remove the manual thumbturn at the main entry/exit door, provide lever hardware at all locations as indicated on plans, no fire sprinkler protection has been provided for the mech/utility room on the first floor, need to final fire sprinkler permit prior to life safety final.
BLD07-01440 FIRE-Final Inspection9/17/20079/17/20079/17/2007 11:01:37 AMPCANC
Scheduled by a contractor via Hello! on 9/17/2007 at 7:14:44 AM. Contact: ###-####. Inspection cancelled from web by: Cathy Weisshaupt