FIR08-00531
| INSP-Sprinkler Rough-in/Hydro | 9/17/2008 | 9/17/2008 | 9/18/2008 3:26:59 PM | P | PASS |
|
|
The overhead hydro test passed.
|
BLD07-00143
| FIRE-Final Inspection | 9/17/2008 | 9/17/2008 | 9/18/2008 1:37:42 PM | P | PASS |
|
|
LIfe safety passed.
|
FIR08-00540
| INSP-Alarm Testing | 9/16/2008 | 9/17/2008 | 9/17/2008 4:51:45 PM | A | PASS |
|
|
Vesda testing completed. Test interconnection to main fire alarm panel Also do a full function test to the pre-action system.KR
|
FIR08-00203
| INSP-Final Inspection | 9/15/2008 | 9/17/2008 | 9/17/2008 4:48:10 PM | A | PASS |
|
|
Testing for pre-action system completed. Tested interconnection to fire alarm panel also performed a foward flush. KR
|
FIR08-00529
| INSP-Final Inspection | 9/16/2008 | 9/17/2008 | 9/17/2008 4:42:12 PM | A | PASS |
|
|
Fire alarm testing completed, all repairs made per last inspection. KR
|
BLD08-01596
| FIRE-Final Inspection | 9/17/2008 | 9/17/2008 | 9/17/2008 3:38:48 PM | P | CANC |
|
|
Wrong inspection type called in.
|
FIR08-00299
| INSP-Sprinkler Rough-in/Hydro | 9/17/2008 | 9/17/2008 | 9/17/2008 3:37:57 PM | P | PASS |
|
|
See the city approved plans for locations where the sprinkler piping can be covered.
|
BLD08-01786
| FIRE-Final Inspection | 9/16/2008 | 9/17/2008 | 9/17/2008 2:05:51 PM | P | PASS |
|
|
LIfe safety passed
|
FIR08-00556
| INSP-Final Inspection | 9/16/2008 | 9/17/2008 | 9/17/2008 2:03:16 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00266
| INSP-Final Inspection | 9/11/2008 | 9/17/2008 | 9/17/2008 1:47:54 PM | P | FAIL |
|
|
Everything tested ok except the strobe in the mens restroom did not function, the sample tubes in the duct smoke detectors are not in the correct holes and the exhaust tubes need to be shortened per the installation guide. Also the strobes do not stop flashing when the horns are silenced as required per NFPA 72.
|
FIR08-00246
| INSP-Final Inspection | 9/9/2008 | 9/17/2008 | 9/17/2008 11:03:43 AM | A | FAIL |
|
|
The technician and I were not able to test the duct smoke detectors today due to not being able to put the detectors into heat mode for testing. Zone 7 indeterminant signal has not been checked either. The abandoned duct smoke detectors need to be removed as per IFC 901.4.4 and the wiring needs to be removed per NFPA 70 (NEC) 760.3 (a). The audio/visuals did test ok.
|