ELE09-01744
| Rough-In Permanent Service | 9/17/2009 | 9/17/2009 | 9/18/2009 9:12:26 AM | A | PASS |
|
|
Around 10 if you can. Phone #: ###-#### Internet Inspection Request from: Brandon Blackham ric ok, p/s u/g n ok, NOTE: met contractor, told to call for u/g inspection fron house to garage and to post addresses, told to change room count and add service
|
ELE09-01354
| Final | 9/17/2009 | 9/17/2009 | 9/17/2009 3:53:04 PM | P | CANC |
|
|
Jared Phone #: ###-#### done in am 9-17-09
|
ESC09-00332
| General Inspection | 9/17/2009 | 9/17/2009 | 9/17/2009 3:52:11 PM | P | PASS |
|
|
looked ok
|
ESC09-00530
| General Inspection | 9/17/2009 | 9/17/2009 | 9/17/2009 3:35:41 PM | P | PASS |
|
|
looked ok
|
ESC09-00342
| General Inspection | 9/17/2009 | 9/17/2009 | 9/17/2009 3:35:00 PM | P | PART |
|
|
looked ok in front, no access to back due to dogs
|
ESC09-00468
| General Inspection | 9/17/2009 | 9/17/2009 | 9/17/2009 3:33:57 PM | P | PASS |
|
|
looked ok
|
ELE09-01554
| Final | 9/17/2009 | 9/17/2009 | 9/17/2009 3:33:11 PM | P | FAIL |
|
|
dan - please call for access Phone #: ###-#### called contractor, told that he needs to fix life safety items before final- such as dead front for electrical panel, to call back when job is cleaned up, no esc this project
|
ELE09-01523
| Final | 9/17/2009 | 9/17/2009 | 9/17/2009 3:14:11 PM | P | PASS |
|
|
Requesting Electrical Final of kitchen remodel Phone #: ###-#### Internet Inspection Request from: Tim Lawrence ok to final, no esc this project
|
ELE09-01769
| Permanent Service | 9/17/2009 | 9/17/2009 | 9/17/2009 2:39:04 PM | P | FAIL |
|
|
Phone #: ###-#### callec contractor, explained that for service turn on they have to bring up to code, and that they have to get ready before inspection such as cut sticker bush so can look at service, grounding must be brought up to code no esc this project
|
ELE08-03233
| Final | 9/16/2009 | 9/17/2009 | 9/17/2009 1:47:12 PM | P | FAIL |
|
|
This will be a final inspection please, Contact is Dennis. Thank you for everything and have a great day! Phone #: ###-#### Internet Inspection Request from: Laura Longshaw met contractor and 412 for inspection with 370, left correction notice,NEC 200.2(B) grounded conductor shall not depend on a connection to a metallic enclosure for continuity, 250.119(A) (1) shall identify grounding conductors for equipment, 312.5 shall provide abrasion protection for all conductors entering enclosures, no esc this project
|
ELE09-01722
| Permanent Service | 9/16/2009 | 9/17/2009 | 9/17/2009 10:47:14 AM | A | NH |
|
|
Phone #: ###-#### Internet Inspection Request from: Lloyd Looney dogs in yard, called, left message, fee due
|
ELE09-01763
| Electrical Rough-In | 9/17/2009 | 9/17/2009 | 9/17/2009 10:05:34 AM | A | PASS |
|
|
Back door to bedroom unlocked please go through back gate and follow plywood, if you need someone there please call me at ###-#### half an hour before inspection. Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ric ok, no esc this project
|
ELE09-01354
| Final | 9/17/2009 | 9/17/2009 | 9/17/2009 9:33:52 AM | A | PASS |
|
|
corrections made, ok to final, no card to sign
|
ELE09-01193
| Final | 9/16/2009 | 9/17/2009 | 9/17/2009 9:08:54 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Dave Friend ok to final, no esc this project
|
ELE09-01756
| Electrical Rough-In | 9/16/2009 | 9/17/2009 | 9/17/2009 8:41:14 AM | A | PART |
|
|
Bud Phone #: ###-#### ok to cover walls only in dressing room only, no green sticker posted, no esc this project
|
ELE09-01741
| Electrical Rough-In | 9/16/2009 | 9/17/2009 | 9/17/2009 8:05:58 AM | A | PASS |
|
|
Jared ###-#### first thing in am ric ok
|