Inspections for the day of: Thursday, September 17, 2009.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00374 FIR-Aging Inspection9/17/20099/17/20099/17/2009 5:46:51 PM DONE
Work in progress
FIR09-00375 FIR-Aging Inspection9/17/20099/17/20099/17/2009 5:46:07 PM DONE
Work in progress
BLD09-00656 FIRE-Final Inspection9/15/20099/17/20099/17/2009 5:44:51 PMAPASS
Fire life safety passed inspection, project related FIR09-00391 scope of work tested with the adjacent truck maintenance and dispatch building fire alarm permit work.
FIR09-00449 INSP-Conference9/17/20099/17/20099/17/2009 5:39:06 PMPDONE
On site conference regarding overhead permit work. Discussed NFPA 13 2007 sec. 8.15.7.1.
BLD09-01204 FIRE-Final Inspection9/17/20099/17/20099/17/2009 5:35:21 PMPPASS
Corrections verified for compliance, EM lighting retest passed, fire life safety finaled.
FIR08-00576 INSP-Final Inspection9/16/20099/17/20099/17/2009 5:34:12 PMAFAIL
Two heads at the second level master bath are obstructed by light fixtures, missing escutcheon at a closet main level, SW head at the stairway is painted, pendent head at the washer/dryer room is too close to an HVAC vent, head at the main level vestibule is blocked by a light fixture.
FIR08-00839 INSP-Final Inspection9/16/20099/17/20099/17/2009 5:27:12 PMAPASS
Correction item field verified for completion, fire sprinkler permit finaled.
FIR08-00831 INSP-Sprinkler Rough-in/Hydro9/16/20099/17/20099/17/2009 5:24:22 PMAPART
Dry system hydrostatic test at building B manifold completed acceptable.
FIR08-00830 INSP-Sprinkler Rough-in/Hydro9/16/20099/17/20099/17/2009 5:22:43 PMAPART
First floor wet system hydrostatic test passed.
BLD07-02143 FIRE-Final Inspection9/16/20099/17/20099/17/2009 2:09:20 PMAPASS
Corrections field verified for completion, fire life safety final approved.
BLD08-01148 FIRE-Final Inspection9/15/20099/17/20099/17/2009 2:08:34 PMPPASS
Fire life safety finaled.
BLD08-01147 FIRE-Final Inspection9/15/20099/17/20099/17/2009 2:08:11 PMPPASS
Fire life safety finaled.
FIR08-00448 INSP-Final Inspection9/17/20099/17/20099/17/2009 2:07:46 PMPPASS
Fire sprinkler permit finaled.
FIR07-01031 INSP-Sprinkler Rough-in/Hydro9/14/20099/17/20099/17/2009 12:00:00 AMPCANC
James Phone #: ###-####
FIR07-01032 INSP-Sprinkler Rough-in/Hydro9/14/20099/17/20099/17/2009 12:00:00 AMPCANC
James Phone #: ###-####