ELE10-01360
| ELE-Aging Inspection | 9/17/2010 | 9/17/2010 | 9/20/2010 6:21:23 AM | | DONE |
|
|
suc
|
ELE09-00253
| ELE-Aging Inspection | 9/17/2010 | 9/17/2010 | 9/20/2010 6:20:38 AM | | DONE |
|
|
see doc expire
|
ELE10-02024
| Electrical Rough-In | 9/16/2010 | 9/17/2010 | 9/17/2010 2:57:01 PM | P | CANC |
|
|
Contact: Shane Korte - Late afternoon inspection if possible please Phone #: ###-#### >> Inspection requested via web by Deb Gooden yalked to electrician, needed several more hours before ready, will call for early Monday
|
ELE10-01957
| Electrical Rough-In | 9/16/2010 | 9/17/2010 | 9/17/2010 2:52:06 PM | A | FAIL |
|
|
Reham Phone #: ###-#### met owner, needs to provide 1 1/4" for holes and nm cable on studs, staple nm within 8" of box
|
ELE10-02065
| Final | 9/17/2010 | 9/17/2010 | 9/17/2010 2:33:01 PM | A | FAIL |
|
|
ALL THE UP TO THE END OF 36TH Phone #: ###-#### >> Inspection requested via web by Bob Glenn called, left correction notice, NEC 250.24(C) shall install main bonding jumper, fee due Note corrections shall be made in 5 working days
|
ELE10-02063
| Rough-In Permanent Service | 9/16/2010 | 9/17/2010 | 9/17/2010 1:57:25 PM | A | FAIL |
|
|
call for access Phone #: ###-#### >> Inspection requested via web by John VanZandt called left correction notice, NEC 408.4 shall provide circuit directory, 110.12(A) shall close openings in panel, 250.52(A)(1) shall use interior metal water piping for grounding electrode, 250.56 rod electrodes shall be 6' apart, 210.52 shall provide receptace for closet wall over 2', 110.14(A) shall connect all strands copper to lug at service, 334.15 shall protect cable at water heater and provide disconnect, NOTE corrections shall be made in 5 working days
|
ELE09-01136
| Electrical Rough-In | 9/16/2010 | 9/17/2010 | 9/17/2010 1:01:51 PM | A | PASS |
|
|
Chauncey Phone #: ###-#### corrections made, ri ok
|
ELE10-01354
| Permanent Service | 9/16/2010 | 9/17/2010 | 9/17/2010 12:01:39 PM | P | PASS |
|
|
Nick is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates p/s u/g rec ok
|
ELE10-01611
| Final | 9/16/2010 | 9/17/2010 | 9/17/2010 11:33:05 AM | A | PART |
|
|
Please contact our Wireman Rod at ###-#### at the site and he will escort you to the 2ND Floor. We would like a Final inspection for the work completed throughout the 2ND Floor with the exception of the Library. Thank you. Phone #: ###-#### >> Inspection requested via web by Clint Tate ok for all but library, panel signs, no card
|
ELE10-01818
| Electrical Rough-In | 9/16/2010 | 9/17/2010 | 9/17/2010 11:01:45 AM | A | PASS |
|
|
wiring for the garage outback, the code to get in is 1221, any questions please call, thx, Terry W. Phone #: ###-#### >> Inspection requested via web by Stephen Kren ri garage only- need service equipment, grounding and inspection, called contractor
|
ELE10-01767
| Final | 9/17/2010 | 9/17/2010 | 9/17/2010 8:25:36 AM | A | DONE |
|
|
cell ###-#### Phone #: ###-#### >> Inspection requested via web by Mark M see prior request, 9-16-10
|