ELE12-02316
| Final | 9/17/2012 | 9/17/2012 | 9/17/2012 4:13:00 PM | P | CANC |
|
|
Temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI
|
ELE12-02316
| Temporary Service | 9/17/2012 | 9/17/2012 | 9/17/2012 4:12:48 PM | P | PASS |
|
|
t/s u/g n ok
|
ELE12-01611
| Final | 9/14/2012 | 9/17/2012 | 9/17/2012 4:00:58 PM | P | PASS |
|
|
Inspect after 3:00pm school in session Phone #: ###-#### >> Inspection requested via web by fred lopez final ok
|
ELE12-02269
| Electrical Rough-In | 9/17/2012 | 9/17/2012 | 9/17/2012 2:28:45 PM | P | FAIL |
|
|
For wall rough-in only. Phone #: ###-#### >> Inspection requested via web by Chad McKibben Grounding not complete in metal boxes. NEC 330.12(1) where subject to physical damage 1 1/4 MC inside 2x4 stud 330.30(B) support within 12 in. of device or fixture box
|
ELE12-02297
| Electrical Rough-In | 9/14/2012 | 9/17/2012 | 9/17/2012 1:52:27 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by ERIC CENTERS rough-in ok cover
|
ELE12-02304
| Electrical Rough-In | 9/17/2012 | 9/17/2012 | 9/17/2012 1:20:38 PM | P | PASS |
|
|
mike Phone #: ###-#### rough-in ok cover cans in covered walkway
|
ELE12-02220
| Temporary Service | 9/17/2012 | 9/17/2012 | 9/17/2012 12:58:31 PM | P | PASS |
|
|
Temp pole Phone #: ###-#### >> Inspection requested via web by TOM BICANDI t/s o/h n ok
|
ELE12-02308
| Rough-In Permanent Service | 9/15/2012 | 9/17/2012 | 9/17/2012 12:30:20 PM | P | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson rough-in p/s u/g n ok
|
ELE12-02314
| Conference | 9/14/2012 | 9/17/2012 | 9/17/2012 10:20:28 AM | A | PASS |
|
|
Timothy Phone #: ###-#### Discussed with home owner GFCI W/R receptacles on outside of house.ok
|
GCE12-00133
| GCE-Final | 9/14/2012 | 9/17/2012 | 9/17/2012 9:37:11 AM | A | PASS |
|
|
Scott @ ###-#### xt. 13 final ok
|
ELE12-02311
| Temporary Service | 9/14/2012 | 9/17/2012 | 9/17/2012 8:57:30 AM | A | PASS |
|
|
THANKS, BOB Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE12-01895
| Final | 9/17/2012 | 9/17/2012 | 9/17/2012 8:39:52 AM | A | NR |
|
|
Ryan is on site. Phone #: ###-#### >> Inspection requested via web by Buster Bowen
|