Inspections for the day of: Tuesday, September 17, 2013.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-01669 Final9/17/20139/17/20139/17/2013 3:36:38 PMPPASS
Garage entrance code 1979E Phone #: ###-#### >> Inspection requested via web by Alan Lusk ok final
ELE13-02454 Final9/12/20139/17/20139/17/2013 3:07:30 PMPPASS
Homeowner will be there Phone #: ###-#### >> Inspection requested via web by Clay Morgan called contractor, ok final
ELE13-02543 Electrical Rough-In9/16/20139/17/20139/17/2013 2:49:39 PMPNR
Solar PV rough in please-Chris Phone #: ###-#### called, told ground shall go to gec for service, not sub-panel, IPCO and NEC requires disconnect by service disconnect along with placards to identify sources and disconnects
ELE13-02553 Electrical Rough-In9/17/20139/17/20139/17/2013 1:57:53 PMPPASS
Phone #: ###-#### >> Inspection requested via web by shane miller rules out of date for conductors at comercial site, ri ok, will see p/s at site
ELE13-02293 Electrical Rough-In9/17/20139/17/20139/17/2013 1:18:09 PMPPASS
Contact: Casey Fouts, partial final please Phone #: ###-#### >> Inspection requested via web by Deb Gooden east walls and ceiling only ok cover
ELE13-02495 Rough-In Permanent Service9/17/20139/17/20139/17/2013 12:20:32 PMPPASS
need rough in and permanent service inspection. Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins open walls only ok cover, will see rest for cut in boxes, p/s o/h rec ok
ELE13-02535 Electrical Rough-In9/16/20139/17/20139/17/2013 11:42:34 AMPPASS
Randy. Wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy walls only ok cover
ELE13-02015 Final9/17/20139/17/20139/17/2013 11:06:42 AMAPASS
Call Dene for access code
thank you Phone #: ###-#### >> Inspection requested via web by kim grundhauser ok final
ELE13-02553 Final9/16/20139/17/20139/17/2013 9:51:08 AMAFAIL
Address to inspect mobile office is 4278 Riva Ridge Boise Id Phone #: ###-#### >> Inspection requested via web by shane miller called contractor, BCC commercial building shall not be wired with nm cable, but shall use mc cable or metal raceways and boxes
ELE13-02315 Electrical Rough-In9/17/20139/17/20139/17/2013 9:48:48 AMPCANC
Contact: Casey Fouts, partial final please Phone #: ###-#### >> Inspection requested via web by Deb Gooden Inspection cancelled from web by: Deb Gooden
ELE13-01461 Final9/16/20139/17/20139/17/2013 9:30:39 AMAPASS
Please call Dianne at ###-#### 30min ahead for access. Thank you. Phone #: ###-#### >> Inspection requested via web by Brad Girard ok final
ELE13-02564 Electrical Rough-In9/16/20139/17/20139/17/2013 9:06:40 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Shaun Kirkman ri ok, jetted tub, recpt in closet behind
ELE13-02522 Final9/16/20139/17/20139/17/2013 8:57:47 AMAPASS
Wired new heat pump, any questions call Andy @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose ok final
ELE13-02522 Electrical Rough-In9/17/20139/17/20139/17/2013 8:38:08 AMAPASS
Wired new heat pump, any questions call Andy @ ###-#### Phone #: ###-#### >> Inspection requested via web by Andy Rose ri ok
ELE13-02016 Rough-In Permanent Service9/17/20139/17/20139/17/2013 8:34:05 AMAPASS
request rough-in/wall cover for all walls to 10'' and bathroom ceilings. All other areas are drop ceiling Phone #: ###-#### >> Inspection requested via web by David Mackey hard lids baths, walls ok cover, p/s u/g n ok
ELE13-02070 Rough-In Permanent Service9/16/20139/17/20139/17/2013 8:07:06 AMAPASS
Mucho Phone #: ###-#### called, corrections made, ri ok, p/s u/g n ok