Inspections for the day of: Wednesday, September 17, 2014.
Number of inspections: 44
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE14-02267 Final9/16/20149/17/20149/17/2014 4:37:51 PMPPASS
Please provide a final inspection for the NRM TI. Call Greg with questions ###-####. Phone #: ###-#### Inspection requested via web by Kevin Perez final ok
ELE14-00817 Final9/16/20149/17/20149/17/2014 4:11:37 PMPFAIL
Phone #: ###-#### Inspection requested via web by Jim Williams please program floor heat tstat so we can test GFCI. Identify garage disconnect as "disconnects"
ELE14-02464 Electrical Rough-In9/16/20149/17/20149/17/2014 3:28:48 PMPPASS
Soffit inspection for recessed cans outside. Phone #: ###-#### Inspection requested via web by Zane Robertson r/i soffits ok
ELE14-02598 Permanent Service9/17/20149/17/20149/17/2014 3:02:11 PMPNR
Paul. Phone #: ###-#### Inspection requested via web by Sean DeLacy was called in for 9/18/14 according to RME. called and asked camille to call back in
ELE14-02567 Final9/12/20149/17/20149/17/2014 2:33:46 PMPNH
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan no answer
ELE14-02567 Electrical Rough-In9/12/20149/17/20149/17/2014 2:22:28 PMPNH
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan no answer
ELE14-02566 Final9/12/20149/17/20149/17/2014 2:21:54 PMPFAIL
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan dryer recep. ok no permit fro new panel
ELE14-02566 Electrical Rough-In9/12/20149/17/20149/17/2014 2:20:57 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok dryer recep. only
ELE14-02565 Final9/12/20149/17/20149/17/2014 2:20:13 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02565 Electrical Rough-In9/12/20149/17/20149/17/2014 2:19:50 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02564 Final9/12/20149/17/20149/17/2014 2:19:19 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02564 Electrical Rough-In9/12/20149/17/20149/17/2014 2:18:49 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02563 Final9/12/20149/17/20149/17/2014 2:18:04 PMPFAIL
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan breaker not labeled
ELE14-02563 Electrical Rough-In9/12/20149/17/20149/17/2014 2:17:27 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02562 Final9/12/20149/17/20149/17/2014 2:16:56 PMPNH
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan no answer
ELE14-02562 Electrical Rough-In9/12/20149/17/20149/17/2014 2:16:23 PMPNH
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan no answer
ELE14-02561 Final9/12/20149/17/20149/17/2014 2:15:46 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02561 Electrical Rough-In9/12/20149/17/20149/17/2014 2:15:21 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02560 Final9/12/20149/17/20149/17/2014 2:14:53 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02560 Rough-In Permanent Service9/12/20149/17/20149/17/2014 2:14:30 PMPCANC
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan needed r/i
ELE14-02560 Electrical Rough-In9/17/20149/17/20149/17/2014 2:13:54 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02559 Final9/12/20149/17/20149/17/2014 2:11:42 PMPFAIL
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan dryer outlet ok no permit for new panel
ELE14-02559 Electrical Rough-In9/12/20149/17/20149/17/2014 2:10:56 PMPFAIL
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan dryer recep. ok no permit for new panel
ELE14-02558 Final9/12/20149/17/20149/17/2014 2:09:04 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02558 Electrical Rough-In9/12/20149/17/20149/17/2014 2:08:28 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02556 Final9/12/20149/17/20149/17/2014 2:07:30 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02556 Electrical Rough-In9/12/20149/17/20149/17/2014 2:02:39 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02555 Final9/12/20149/17/20149/17/2014 2:00:15 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02555 Electrical Rough-In9/12/20149/17/20149/17/2014 1:59:44 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02554 Final9/12/20149/17/20149/17/2014 1:59:17 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02554 Electrical Rough-In9/12/20149/17/20149/17/2014 1:58:40 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02553 Final9/12/20149/17/20149/17/2014 1:57:56 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02553 Electrical Rough-In9/12/20149/17/20149/17/2014 1:57:28 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE14-02553 Electrical Rough-In9/12/20149/17/20149/17/2014 1:56:50 PMPCANC
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan called in twice
ELE14-02552 Final9/12/20149/17/20149/17/2014 1:52:50 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan final ok
ELE14-02552 Electrical Rough-In9/12/20149/17/20149/17/2014 1:51:59 PMPPASS
Please call Nelda ###-#### when you are on your way. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan r/i ok
ELE13-01291 Electrical Rough-In9/17/20149/17/20149/17/2014 1:05:07 PMPPASS
Phone #: ###-#### Inspection requested via web by Tom Betty go over fat grid ceiling submittals to confirm installation is acceptable. Additional supports have been installed onthese ceilings. r/i ok part of 3rd level ceiling helix
ELE14-02601 Electrical Rough-In9/17/20149/17/20149/17/2014 11:21:25 AMAPASS
new bathroom walls, ceiling and misc doors for the mag holders Phone #: ###-#### Inspection requested via web by Karl Paige r/i ok short wall near entrance and door holders and womens showers
ELE14-02602 Electrical Rough-In9/17/20149/17/20149/17/2014 10:44:58 AMAPASS
Phone #: ###-#### Inspection requested via web by PAUL PINNEY r/i ok
GCE14-00151 GCE-Rough-In9/16/20149/17/20149/17/2014 10:11:48 AMAPASS
###-#### r/i ok
GCE14-00146 GCE-Rough-In9/16/20149/17/20149/17/2014 9:14:01 AMADONE
Creek ###-#### spoke with TARA and she thought there were corrections here but none are shown
ELE12-02554 ELE-Aging Inspection9/17/20149/17/20149/17/2014 7:57:42 AM DONE
too busy
ELE12-02541 ELE-Aging Inspection9/17/20149/17/20149/17/2014 7:57:13 AM DONE
too busy
ELE11-02792 ELE-Aging Inspection9/17/20149/17/20149/17/2014 7:56:47 AM DONE
too busy