ELE15-02716
| Final | 9/17/2015 | 9/17/2015 | 9/17/2015 3:09:32 PM | P | PASS |
|
|
Mike-please call 30 minutes prior to meet Phone #: ###-#### final ok
|
ELE15-02706
| Final | 9/17/2015 | 9/17/2015 | 9/17/2015 3:07:55 PM | P | PASS |
|
|
Mike-please call 30 minutes prior to meet Phone #: ###-#### final ok
|
ELE15-02963
| Final | 9/16/2015 | 9/17/2015 | 9/17/2015 2:46:38 PM | P | PASS |
|
|
Inspection requested via web by Kelly Felin final ok
|
ELE15-02963
| Permanent Service | 9/17/2015 | 9/17/2015 | 9/17/2015 2:38:06 PM | P | PASS |
|
|
Inspection requested via web by Kelly Felin p/s o/h rec ok already hooked up, work done after hours
|
ELE15-02889
| Final | 9/17/2015 | 9/17/2015 | 9/17/2015 2:11:08 PM | P | PASS |
|
|
Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates final ok
|
GCE14-00207
| GCE-Permanent Service | 9/17/2015 | 9/17/2015 | 9/17/2015 1:54:33 PM | P | PASS |
|
|
Kevin ###-#### - service insp. for structure p/s u/g n ok (this p/s request is for meters for units) located in service no. 1 so. west corner of complex
|
GCE14-00207
| GCE-Final | 9/17/2015 | 9/17/2015 | 9/17/2015 1:51:58 PM | P | CANC |
|
|
Kevin ###-#### - streetlight final needs public works inspection for light poles..(Needs p/s insp. for power to pedestal from city of boise for meter)
|
ELE15-02958
| Electrical Rough-In | 9/16/2015 | 9/17/2015 | 9/17/2015 11:34:47 AM | A | PASS |
|
|
wall cover call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig r/i walls ok
|
ELE15-02878
| Rough-In Permanent Service | 9/15/2015 | 9/17/2015 | 9/17/2015 11:16:02 AM | A | PASS |
|
|
ROUGH IN PERMANENT SERVICE. CHANGING FROM OVERHEAD POWER TO UNDERGROUND POWER. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld r/i not needed p/s u/g n ok will look for irreversable grounding electrode conductor connection during remodel
|
ELE15-02964
| Rough-In Permanent Service | 9/16/2015 | 9/17/2015 | 9/17/2015 10:38:34 AM | A | PASS |
|
|
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER r/i not needed at this time p/s o/h rec ok
|
ELE15-01794
| Final | 9/16/2015 | 9/17/2015 | 9/17/2015 10:19:04 AM | A | PASS |
|
|
Dan garage code- 1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey final ok
|
ELE15-02434
| Final | 9/16/2015 | 9/17/2015 | 9/17/2015 9:38:22 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe FINAL OK
|
GCE15-00146
| GCE-Final | 9/16/2015 | 9/17/2015 | 9/17/2015 8:53:26 AM | A | FAIL |
|
|
Jay ###-#### - meter base repair 250.52(A)(1)-metal underground water pipe needs #6 bare copper conductor bonded within first 5 feet of entering structure. 250.52(A)(5)- at least 2 8'X1/2" ground rods driven more than 6 ' apart with #6 bare copper conductor to main disconnect. 250.24(A)- a premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor. 250.94-an intersystem bonding termination for connecting intersystem bonding conductors required for other systems shall be provided with a # 6 bare copper conductor. NOTE; CALL FOR PERMANENT SERVICE WHEN READY AND CALL FOR FINAL ALSO.
|