Inspections for the day of: Thursday, September 17, 2015.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE15-02716 Final9/17/20159/17/20159/17/2015 3:09:32 PMPPASS
Mike-please call 30 minutes prior to meet Phone #: ###-#### final ok
ELE15-02706 Final9/17/20159/17/20159/17/2015 3:07:55 PMPPASS
Mike-please call 30 minutes prior to meet Phone #: ###-#### final ok
ELE15-02963 Final9/16/20159/17/20159/17/2015 2:46:38 PMPPASS
Inspection requested via web by Kelly Felin final ok
ELE15-02963 Permanent Service9/17/20159/17/20159/17/2015 2:38:06 PMPPASS
Inspection requested via web by Kelly Felin p/s o/h rec ok already hooked up, work done after hours
ELE15-02889 Final9/17/20159/17/20159/17/2015 2:11:08 PMPPASS
Shane is the contact his cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates final ok
GCE14-00207 GCE-Permanent Service9/17/20159/17/20159/17/2015 1:54:33 PMPPASS
Kevin ###-#### - service insp. for structure p/s u/g n ok (this p/s request is for meters for units) located in service no. 1 so. west corner of complex
GCE14-00207 GCE-Final9/17/20159/17/20159/17/2015 1:51:58 PMPCANC
Kevin ###-#### - streetlight final needs public works inspection for light poles..(Needs p/s insp. for power to pedestal from city of boise for meter)
ELE15-02958 Electrical Rough-In9/16/20159/17/20159/17/2015 11:34:47 AMAPASS
wall cover call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig r/i walls ok
ELE15-02878 Rough-In Permanent Service9/15/20159/17/20159/17/2015 11:16:02 AMAPASS
ROUGH IN PERMANENT SERVICE. CHANGING FROM OVERHEAD POWER TO UNDERGROUND POWER. Phone #: ###-#### Inspection requested via web by Daniel Schaffeld r/i not needed p/s u/g n ok will look for irreversable grounding electrode conductor connection during remodel
ELE15-02964 Rough-In Permanent Service9/16/20159/17/20159/17/2015 10:38:34 AMAPASS
call first, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER r/i not needed at this time p/s o/h rec ok
ELE15-01794 Final9/16/20159/17/20159/17/2015 10:19:04 AMAPASS
Dan garage code- 1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey final ok
ELE15-02434 Final9/16/20159/17/20159/17/2015 9:38:22 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe FINAL OK
GCE15-00146 GCE-Final9/16/20159/17/20159/17/2015 8:53:26 AMAFAIL
Jay ###-#### - meter base repair 250.52(A)(1)-metal underground water pipe needs #6 bare copper conductor bonded within first 5 feet of entering structure. 250.52(A)(5)- at least 2 8'X1/2" ground rods driven more than 6 ' apart with #6 bare copper conductor to main disconnect. 250.24(A)- a premises wiring system supplied by a grounded ac service shall have a grounding electrode conductor connected to the grounded service conductor. 250.94-an intersystem bonding termination for connecting intersystem bonding conductors required for other systems shall be provided with a # 6 bare copper conductor. NOTE; CALL FOR PERMANENT SERVICE WHEN READY AND CALL FOR FINAL ALSO.