Inspections for the day of: Monday, September 17, 2018.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR18-00632 INSP-Sprinkler Rough-in9/14/20189/17/20189/18/2018 12:00:00 AMPPASS
Phone #: ###-#### >> Inspection requested via web by Stan Beus
Rough in ok. Insulation compatibility with CPVC to be verified.

_____________
Compatibility is verified. See attached document. 9/18/2018 TRF
FIR18-00680 INSP-Sprinkler Rough-in/Hydro9/17/20189/17/20189/18/2018 12:00:00 AMPPASS
Underground rough/hydro. Call Anthony with a time, will be ready this morning Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello

_____________
Udg installation appeard to be adequate.
One hydro held fine, no loss.
The second hydro was low when I arrived. The contractor showed up and fixed a leak where the guage was connected. When I arrived the second time the UDG appeared to be holding pressure. I saw no visible leakeage.
NAF18-00108 INSP-Final9/17/20189/17/20189/17/2018 12:00:00 AMPCANC
Call prior to going Phone #: 2084125969 >> Inspection requested via mobile web by John Wood.

Inspection was requested by the building owner. Contractors were not present so inspection was canceled. Contractors are to call in for a new inspection date and be present.
FIR18-00632 INSP-Sprinkler Rough-in9/14/20189/17/20189/14/2018 10:37:30 AMACANC
Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus