Inspections for the day of: Wednesday, September 18, 2002.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-00972 FIRE-Final Inspection9/17/20029/18/20029/18/2002 12:00:00 AMAPASS
###-####
BLD02-00324 FIRE-Final Inspection9/17/20029/18/20029/18/2002 12:00:00 AMAPASS
BLD02-01986 FIRE-Final Inspection9/17/20029/18/20029/18/2002 12:00:00 AMAPASS
FIR02-00095 INSP-Final Inspection9/18/20029/18/20029/18/2002 12:00:00 AMAFAIL
fire shutter not closing on alarm
BLD01-03067 FIRE-Final Inspection9/16/20029/18/20029/18/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 09/16/2002 at 14:23:46. Contact: ###-####. need label on south door; penetrations in corridor wall; firestopping at fire shutter counter (underneath); fire shutter not closing 9/18/2002 8:45:50 AM
FIR02-00353 INSP-Sprinkler Rough-in/Hydro9/17/20029/18/20029/18/2002 12:00:00 AMPFAIL
###-#### james need retaining straps and to verify main EQ for this floor; need spare heads 9/18/2002 3:07:03 PM
BLD02-01628 FIRE-Conference9/18/20029/18/20029/18/2002 12:00:00 AMPPART
met with GC while doing a sprinkler rough in; fire plan review notes indicated fire alarm plans were needed; checked alarm panel and it requires smoke detector above panel and 60 hour of batteries; the building is sprinklered and requires off site monitoring; the building has pull stations and the old style strobes with red lenses (not compliant with ADA) and horns; this tenant has several AHU's that appear to require detectors for shutdown (common plenum and no mechanical plans)