BLD01-00972
| FIRE-Final Inspection | 9/17/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | A | PASS |
|
|
###-####
|
BLD02-00324
| FIRE-Final Inspection | 9/17/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | A | PASS |
|
|
|
BLD02-01986
| FIRE-Final Inspection | 9/17/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | A | PASS |
|
|
|
FIR02-00095
| INSP-Final Inspection | 9/18/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | A | FAIL |
|
|
fire shutter not closing on alarm
|
BLD01-03067
| FIRE-Final Inspection | 9/16/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 09/16/2002 at 14:23:46. Contact: ###-####. need label on south door; penetrations in corridor wall; firestopping at fire shutter counter (underneath); fire shutter not closing 9/18/2002 8:45:50 AM
|
FIR02-00353
| INSP-Sprinkler Rough-in/Hydro | 9/17/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | P | FAIL |
|
|
###-#### james need retaining straps and to verify main EQ for this floor; need spare heads 9/18/2002 3:07:03 PM
|
BLD02-01628
| FIRE-Conference | 9/18/2002 | 9/18/2002 | 9/18/2002 12:00:00 AM | P | PART |
|
|
met with GC while doing a sprinkler rough in; fire plan review notes indicated fire alarm plans were needed; checked alarm panel and it requires smoke detector above panel and 60 hour of batteries; the building is sprinklered and requires off site monitoring; the building has pull stations and the old style strobes with red lenses (not compliant with ADA) and horns; this tenant has several AHU's that appear to require detectors for shutdown (common plenum and no mechanical plans)
|