Inspections for the day of: Tuesday, September 18, 2007.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03234 Electrical Rough-In9/17/20079/18/20079/18/2007 4:05:02 PMPPASS
James; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ri ok
ELE07-03234 Final9/18/20079/18/20079/18/2007 4:04:24 PMPPASS
James; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE07-01849 Final9/18/20079/18/20079/18/2007 3:26:20 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung ok to final
ELE07-02667 Electrical Rough-In9/17/20079/18/20079/18/2007 2:16:41 PMPFAIL
lawrence Phone #: ###-#### met owner, left corr notice, nec 300.5 pvc shall be min 18" deep to top of conduit, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 314.16(C) only conduit bodies marked by manfacturers with their volume shall be permitted to contain splices and they shall be supported in a rigid manner, 110.14 connections shall be properly installed for ground lugs (use crimping tool)
ELE07-03223 Final9/18/20079/18/20079/18/2007 1:23:23 PMPPASS
###-#### please call me a half hour before so I can meet you there Thank You, Todd Internet Inspection Request from: Todd Holbrook met contr, signed structural card, ok to final
ELE07-02506 Final9/18/20079/18/20079/18/2007 12:49:37 PMPPASS
the point of sale is ready for the final inspection Phone #: ###-#### Internet Inspection Request from: Scott Abbott ok to final, signed occupancy card
ELE07-02395 Final9/18/20079/18/20079/18/2007 11:43:56 AMAPASS
###-#### - lynn ok to final
ELE07-02394 Final9/18/20079/18/20079/18/2007 11:43:21 AMAPASS
###-#### - lynn ok to final
ELE07-02392 Final9/18/20079/18/20079/18/2007 10:38:44 AMAPASS
###-#### - lynn ok to final
ELE07-02393 Final9/18/20079/18/20079/18/2007 10:20:43 AMAPASS
###-#### - lynn ok to final
ELE07-02391 Final9/18/20079/18/20079/18/2007 9:53:57 AMAPASS
###-#### - lynn ok to final
ELE07-02013 Final9/18/20079/18/20079/18/2007 9:34:00 AM PASS
###-#### - lynn ok to final
ELE07-02011 Final9/18/20079/18/20079/18/2007 9:21:30 AMAPASS
###-#### - lynn ok to final
ELE07-02012 Final9/18/20079/18/20079/18/2007 9:07:44 AMAPASS
###-#### - lynn ok to final
ELE07-02014 Final9/18/20079/18/20079/18/2007 8:45:56 AMAPASS
###-#### - lynn ok to final
ELE07-03236 Final9/18/20079/18/20079/18/2007 7:57:48 AMACANC
Temp pole Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman see t/s, wrong type request
ELE07-03236 Temporary Service9/18/20079/18/20079/18/2007 7:57:24 AMAPASS
Temp pole Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman called contr, t/s u/g n ok