Inspections for the day of: Tuesday, September 18, 2007.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00685 INSP-Sprinkler Rough-in/Hydro9/18/20079/18/20079/19/2007 10:52:32 AMPFAIL
New upright heads are overspaced at the open work area, overhead install at the drop ceilings is approved for cover.
BLD07-01698 FIRE-Final Inspection9/18/20079/18/20079/18/2007 4:26:40 PMPPASS
Fire life safety inspection passed, missing suite numbers to be installed per contractor agreement.
BLD07-01440 FIRE-Final Inspection9/17/20079/18/20079/18/2007 3:01:17 PMAPASS
Fire life safety passed inspection, manual flush bolts at the main entry/exit door inactive leaf to be replaced with automatic bolts prior to sturctural final as discussed with contractor.
FIR07-00617 INSP-Final Inspection9/18/20079/18/20079/18/2007 1:59:40 PMPPASS
Required changes have been completed, some issues repaired while on site, signals verified, fire alarm permit finaled.
FIR07-00252 FIR-Aging Inspection9/18/20079/18/20079/18/2007 1:52:19 PM DEFR
Under construction, work in progress.
FIR07-00740 INSP-Final Inspection9/17/20079/18/20079/18/2007 1:50:39 PMAPASS
Install had been covered prior to rough-in inspection request, contractor was provided on site to expose work for inspection as needed, noted three retaining straps at beam clamps which were not secured correctly-contractor agreed to repair today, need to install missing ceiling tile at the corridor, field modifications in pipe routing noted and accepted, fire sprinkler permit finaled.
BLD05-00038 FIRE-Final Inspection9/17/20079/18/20079/18/2007 1:37:08 PMAPASS
Items from the previous correction notice have been verified for completion, noted the provided PFE is past due annual certification-tenant has made arrangements for testing today, no card available for signature on site.
FIR07-00475 INSP-Final Inspection9/17/20079/18/20079/18/2007 1:30:48 PMAPASS
Fire alarm work passed field testing, permit finaled.
BLD07-01984 FIRE-Final Inspection9/17/20079/18/20079/18/2007 1:29:32 PMAPASS
Life safety is acceptable, noted signage at the main entry/exit door to be installed prior to structural final, locking hardware at the door to the storage mezzanine to be removed as agreed.
FIR07-00344 INSP-Sprinkler Rough-in/Hydro9/17/20079/18/20079/18/2007 11:14:11 AMACANC
Need a rough-in & overhead hydro. Please call 1/2 hour prior to inspection. Jeremy is the contact, thank you. Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus