Inspections for the day of: Tuesday, September 18, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00957 INSP-Final Inspection9/17/20079/18/20079/18/2007 3:54:34 PMPFAIL
Todays inspection covered the modified sprinkler heads in "A" wing 1st, 2nd and 3rd floors. They all look good except for one head was missed in the southwest third floor stairwell ceiling and in the common electrical room that is on all floors.
FIR05-00536 INSP-Sprinkler Rough-in9/18/20079/18/20079/18/2007 3:39:31 PMPPASS
Fifth floor sprinkler piping is ok to cover.
FIR07-00596 INSP-Final Inspection9/13/20079/18/20079/18/2007 3:16:20 PMPPASS
Permit finaled
BLD07-01303 FIRE-Final Inspection9/18/20079/18/20079/18/2007 3:14:06 PMPFAIL
Approved door hardware needs to be provided on the new doors as per note M. The exterior doors need approved hardware provided and the thumbturn lock and manual flush bolts removed and automatics provided.
BLD06-03513 FIRE-Final Inspection9/14/20079/18/20079/18/2007 3:11:33 PMPPASS
Life safety passed.
FIR07-00219 INSP-Final Inspection9/18/20079/18/20079/18/2007 3:01:57 PMPPASS
permit finaled
FIR07-00130 INSP-Final Inspection9/17/20079/18/20079/18/2007 2:26:47 PMAFAIL
The inspection was for the first floor due to time constraints. There was missing ceiling tile in many locations and part of the ceiling is missing in the laundry room. Also it appears acouple of pendants are blocked by the surface mount lights in the conference room.
FIR06-00011 INSP-Alarm Testing9/17/20079/18/20079/18/2007 12:03:43 PMACANC
Mike could not make it today. I notified Brian that he would need to reschedule.
BLD05-00633 FIRE-Final Inspection9/18/20079/18/20079/18/2007 11:55:04 AMPCANC
tom Phone #: ###-####
FIR07-00578 INSP-Sprinkler Rough-in9/14/20079/18/20079/18/2007 11:38:17 AMAPASS
See the city approved plans for piping locations where the piping can be covered.
FIR07-00684 INSP-Final Inspection9/17/20079/18/20079/18/2007 11:27:07 AMAPASS
Permit finaled. The hood suppression system operated correctly.
BLD07-01829 FIRE-Final Inspection9/17/20079/18/20079/18/2007 11:22:10 AMAPASS
Fire life safety passed.
FIR06-00811 INSP-Alarm Testing9/17/20079/18/20079/18/2007 10:08:02 AMADONE
No actual inspection was perform today do to multiple problems found.They include the fire alarm panel does not sound on second alarm. There are many over spaced detectors in lounge area. There are areas where smoke detectors and a/v's need to be added. In the dining areas the cieling mounts a/v'sare know mounted on the walls. The kithen area has same problems as well. The contractor needs to resubmit these changes.