FIR06-00957
| INSP-Final Inspection | 9/17/2007 | 9/18/2007 | 9/18/2007 3:54:34 PM | P | FAIL |
|
|
Todays inspection covered the modified sprinkler heads in "A" wing 1st, 2nd and 3rd floors. They all look good except for one head was missed in the southwest third floor stairwell ceiling and in the common electrical room that is on all floors.
|
FIR05-00536
| INSP-Sprinkler Rough-in | 9/18/2007 | 9/18/2007 | 9/18/2007 3:39:31 PM | P | PASS |
|
|
Fifth floor sprinkler piping is ok to cover.
|
FIR07-00596
| INSP-Final Inspection | 9/13/2007 | 9/18/2007 | 9/18/2007 3:16:20 PM | P | PASS |
|
|
Permit finaled
|
BLD07-01303
| FIRE-Final Inspection | 9/18/2007 | 9/18/2007 | 9/18/2007 3:14:06 PM | P | FAIL |
|
|
Approved door hardware needs to be provided on the new doors as per note M. The exterior doors need approved hardware provided and the thumbturn lock and manual flush bolts removed and automatics provided.
|
BLD06-03513
| FIRE-Final Inspection | 9/14/2007 | 9/18/2007 | 9/18/2007 3:11:33 PM | P | PASS |
|
|
Life safety passed.
|
FIR07-00219
| INSP-Final Inspection | 9/18/2007 | 9/18/2007 | 9/18/2007 3:01:57 PM | P | PASS |
|
|
permit finaled
|
FIR07-00130
| INSP-Final Inspection | 9/17/2007 | 9/18/2007 | 9/18/2007 2:26:47 PM | A | FAIL |
|
|
The inspection was for the first floor due to time constraints. There was missing ceiling tile in many locations and part of the ceiling is missing in the laundry room. Also it appears acouple of pendants are blocked by the surface mount lights in the conference room.
|
FIR06-00011
| INSP-Alarm Testing | 9/17/2007 | 9/18/2007 | 9/18/2007 12:03:43 PM | A | CANC |
|
|
Mike could not make it today. I notified Brian that he would need to reschedule.
|
BLD05-00633
| FIRE-Final Inspection | 9/18/2007 | 9/18/2007 | 9/18/2007 11:55:04 AM | P | CANC |
|
|
tom Phone #: ###-####
|
FIR07-00578
| INSP-Sprinkler Rough-in | 9/14/2007 | 9/18/2007 | 9/18/2007 11:38:17 AM | A | PASS |
|
|
See the city approved plans for piping locations where the piping can be covered.
|
FIR07-00684
| INSP-Final Inspection | 9/17/2007 | 9/18/2007 | 9/18/2007 11:27:07 AM | A | PASS |
|
|
Permit finaled. The hood suppression system operated correctly.
|
BLD07-01829
| FIRE-Final Inspection | 9/17/2007 | 9/18/2007 | 9/18/2007 11:22:10 AM | A | PASS |
|
|
Fire life safety passed.
|
FIR06-00811
| INSP-Alarm Testing | 9/17/2007 | 9/18/2007 | 9/18/2007 10:08:02 AM | A | DONE |
|
|
No actual inspection was perform today do to multiple problems found.They include the fire alarm panel does not sound on second alarm. There are many over spaced detectors in lounge area. There are areas where smoke detectors and a/v's need to be added. In the dining areas the cieling mounts a/v'sare know mounted on the walls. The kithen area has same problems as well. The contractor needs to resubmit these changes.
|