Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00517 INSP-Sprinkler Rough-in/Hydro9/18/20089/18/20089/19/2008 7:27:11 AMPPART
5th floor overhead rough-in at the grid ceilings is approved for cover.
FIR08-00486 INSP-Final Inspection9/17/20089/18/20089/19/2008 7:26:12 AMPNR
Rick- call 30 min prior to going Phone #: ###-####
FIR08-00590 INSP-Final Inspection9/17/20089/18/20089/19/2008 7:25:52 AMPNR
pat Phone #: ###-####
BLD08-01369 FIRE-Final Inspection9/17/20089/18/20089/18/2008 4:45:38 PMAPASS
Life safety completed.No fire sprinkler or fire alarm work was required for this permit.KR
BLD08-01367 FIRE-Final Inspection9/17/20089/18/20089/18/2008 4:05:17 PMAPASS
Life safety completed.No fire sprinkler or fire alarm work was required for this permit.KR
FIR07-00663 INSP-Final Inspection9/17/20089/18/20089/18/2008 3:01:23 PMAFAIL
Per contractor missing cold cavity protection, noted missing escutcheons, lacking tamper switches at the main control and backflow shutoff valves.
FIR08-00512 INSP-Final Inspection9/16/20089/18/20089/18/2008 2:09:19 PMANR
Missing tamper switches at the fire sprinkler main control and DCVA shutoff valves #1 and 2.
BLD07-02837 FIRE-Final Inspection9/17/20089/18/20089/18/2008 2:06:47 PMPNR
Need project related fire sprinkler and alarm permit work tested and finaled prior to building fire life safety approvals. Discussed items needed for final including basic fire code review note conditions.
FIR08-00319 INSP-Sprinkler Rough-in/Hydro9/18/20089/18/20089/18/2008 2:04:41 PMPFAIL
Yard PIV is installed too low, need to provide correct spacing and matched temperature SW heads at the lions den, min. spacing at six upright heads in the kitchen and vending area is exceeded, noted three added heads for exterior canopies have been installed on the antifreeze system that do not show on approved plans, also noted re-routed 2 1/2" main, missing sw stock at the head box, missing outside bell. Forward flow completed okay.
FIR08-00319 INSP-Sprinkler Rough-in/Hydro9/17/20089/18/20089/18/2008 1:53:34 PMAPART
OH hydrostatic testing passed.
FIR08-00319 INSP-Final Inspection9/17/20089/18/20089/18/2008 1:01:02 PMPCANC
Mike B is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus