FIR08-00517
| INSP-Sprinkler Rough-in/Hydro | 9/18/2008 | 9/18/2008 | 9/19/2008 7:27:11 AM | P | PART |
|
|
5th floor overhead rough-in at the grid ceilings is approved for cover.
|
FIR08-00486
| INSP-Final Inspection | 9/17/2008 | 9/18/2008 | 9/19/2008 7:26:12 AM | P | NR |
|
|
Rick- call 30 min prior to going Phone #: ###-####
|
FIR08-00590
| INSP-Final Inspection | 9/17/2008 | 9/18/2008 | 9/19/2008 7:25:52 AM | P | NR |
|
|
pat Phone #: ###-####
|
BLD08-01369
| FIRE-Final Inspection | 9/17/2008 | 9/18/2008 | 9/18/2008 4:45:38 PM | A | PASS |
|
|
Life safety completed.No fire sprinkler or fire alarm work was required for this permit.KR
|
BLD08-01367
| FIRE-Final Inspection | 9/17/2008 | 9/18/2008 | 9/18/2008 4:05:17 PM | A | PASS |
|
|
Life safety completed.No fire sprinkler or fire alarm work was required for this permit.KR
|
FIR07-00663
| INSP-Final Inspection | 9/17/2008 | 9/18/2008 | 9/18/2008 3:01:23 PM | A | FAIL |
|
|
Per contractor missing cold cavity protection, noted missing escutcheons, lacking tamper switches at the main control and backflow shutoff valves.
|
FIR08-00512
| INSP-Final Inspection | 9/16/2008 | 9/18/2008 | 9/18/2008 2:09:19 PM | A | NR |
|
|
Missing tamper switches at the fire sprinkler main control and DCVA shutoff valves #1 and 2.
|
BLD07-02837
| FIRE-Final Inspection | 9/17/2008 | 9/18/2008 | 9/18/2008 2:06:47 PM | P | NR |
|
|
Need project related fire sprinkler and alarm permit work tested and finaled prior to building fire life safety approvals. Discussed items needed for final including basic fire code review note conditions.
|
FIR08-00319
| INSP-Sprinkler Rough-in/Hydro | 9/18/2008 | 9/18/2008 | 9/18/2008 2:04:41 PM | P | FAIL |
|
|
Yard PIV is installed too low, need to provide correct spacing and matched temperature SW heads at the lions den, min. spacing at six upright heads in the kitchen and vending area is exceeded, noted three added heads for exterior canopies have been installed on the antifreeze system that do not show on approved plans, also noted re-routed 2 1/2" main, missing sw stock at the head box, missing outside bell. Forward flow completed okay.
|
FIR08-00319
| INSP-Sprinkler Rough-in/Hydro | 9/17/2008 | 9/18/2008 | 9/18/2008 1:53:34 PM | A | PART |
|
|
OH hydrostatic testing passed.
|
FIR08-00319
| INSP-Final Inspection | 9/17/2008 | 9/18/2008 | 9/18/2008 1:01:02 PM | P | CANC |
|
|
Mike B is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus
|