Inspections for the day of: Thursday, September 18, 2014.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00416 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 3:39:00 PMPCANC
Brandon-underground flushing Phone #: ###-####
FIR14-00419 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 3:38:51 PMPCANC
Brandon-underground flushing Phone #: ###-####
FIR14-00418 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 3:38:42 PMPCANC
Brandon-underground flushing Phone #: ###-####
FIR14-00417 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 3:38:29 PMPCANC
Brandon-underground flushing Phone #: ###-####
FIR14-00356 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 3:38:20 PMPCANC
Brandon-underground flushing Phone #: ###-####
FIR14-00357 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 3:37:08 PMPCANC
Brandon-underground flushing Phone #: ###-####
FIR14-00666 INSP-Final Inspection9/18/20149/18/20149/18/2014 3:04:20 PMPCANC
Todd is on another project and could not meet with the city approved plans.
BLD14-01743 FIRE-Final Inspection9/17/20149/18/20149/18/2014 3:01:21 PMAFAIL
No fire sprinkler plans on site so I could not final the project related fire sprinkler permit
BLD14-01322 FIRE-Final Inspection9/17/20149/18/20149/18/2014 2:33:00 PMPFAIL
Provide exit signs as per the approved plans and panic hardware on the north exit door as per the plans.
FIR14-00551 INSP-Final Inspection9/17/20149/18/20149/18/2014 2:32:25 PMPPASS
Permit finaled
FIR14-00630 INSP-Final Inspection9/16/20149/18/20149/18/2014 2:31:38 PMPFAIL
The north and south duct smoke detectors did not shut down the hvac units immediately as required per IMC 606.2.1. Since the units are less than 2,000cfm I gave Dutch the option of either fixing the shutdown or remove them all together and providing as-builts. The center duct detector and the Ansul hood did test ok.
FIR14-00396 INSP-Sprinkler Rough-in9/18/20149/18/20149/18/2014 12:41:37 PMPPASS
Underground flush passed.
FIR14-00354 INSP-Sprinkler Rough-in/Hydro9/18/20149/18/20149/18/2014 11:54:44 AMPPASS
24 hour air test started on all four dry systems and 10:00am with the pressure marked in red on the guage.
FIR14-00551 INSP-Final Inspection9/17/20149/18/20149/17/2014 11:32:38 AMACANC
Chris to attend Phone #: ###-#### >> Inspection requested via web by Connie Danes Inspection cancelled from web by: Connie Danes