Inspections for the day of: Friday, September 18, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02580 ELE-Aging Inspection9/18/20159/18/20159/18/2015 2:26:45 PM DONE
Waiting on owner
ELE13-00368 ELE-Aging Inspection9/18/20159/18/20159/18/2015 2:22:59 PM DONE
Still under construction
ELE13-00373 ELE-Aging Inspection9/18/20159/18/20159/18/2015 2:11:30 PM DONE
Still under construction
ELE13-00338 ELE-Aging Inspection9/18/20159/18/20159/18/2015 2:10:37 PM DONE
Still under construction
GCE15-00095 GCE-Final9/18/20159/18/20159/18/2015 2:09:00 PMPFAIL
Lewis ###-#### 110.24- Available fault current shall be posted and date value was calculated.
230.70- Main disconnect shall be identified as to its purpose.
330.30- MC cable shall be secured with in 12" of back exit sign.
406.6- Replace broken receptacle plate west wall.
408.4- Circuit directory shall be completed on new panel.
408.7- Existing panels, unused openings shall be closed.
GCE15-00117 GCE-Final9/17/20159/18/20159/18/2015 1:30:15 PMPPASS
Stephanie ###-#### Final ok
ELE15-02331 Final9/18/20159/18/20159/18/2015 12:32:14 PMPFAIL
Inspection requested via web by daniel bibikov 300.15- NM cable shall terminate in a box for the receptacle outlet located in net panel.
ELE15-02086 Final9/17/20159/18/20159/18/2015 11:20:17 AMAPASS
Kevin Phone #: ###-#### Final ok
ELE15-02334 Final9/18/20159/18/20159/18/2015 11:19:52 AMPFAIL
110.26- Works space, minimun of 30" wide and 36" deep shall be maintained for work space for pool panel. 680.21(C)- Outlets supplying pool pump motors shall be provided with GFCI protection. Unable to verify branch circuit feeding pool panel due to no answer at door.
ELE15-02984 Electrical Rough-In9/17/20159/18/20159/18/2015 10:53:42 AMAPASS
code 1427 Phone #: ###-#### Inspection requested via web by kendall bender space 13909 wall rough in ok cover
ELE15-02926 Temporary Service9/18/20159/18/20159/18/2015 10:19:08 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn 590.6- All temporary power provided for construction shall have GFCI protection.
ELE15-02505 Final9/18/20159/18/20159/18/2015 9:55:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
ELE15-01928 Electrical Rough-In9/17/20159/18/20159/18/2015 9:29:45 AMAPASS
wall pack rough in Phone #: ###-#### Inspection requested via web by Scott Campbell 3 additional wall packs west side rough in ok cover
ELE15-02988 Temporary Service9/17/20159/18/20159/18/2015 9:16:16 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
ELE15-01856 Final9/17/20159/18/20159/18/2015 9:01:18 AMAPASS
Dan garage code-1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey Final ok
ELE15-02990 Temporary Service9/18/20159/18/20159/18/2015 8:25:15 AMAPASS
Phone #: ###-#### Inspection requested via web by Shaun Kirkman t/s u/g n ok
ELE15-02545 Electrical Rough-In9/17/20159/18/20159/18/2015 8:13:22 AMAPASS
We are requesting a wall rough-in inspection in the customer service area for Friday 9/18/15 in the AM. Our contact for this is Todd @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Rough in ok cover