ELE12-02580
| ELE-Aging Inspection | 9/18/2015 | 9/18/2015 | 9/18/2015 2:26:45 PM | | DONE |
|
|
Waiting on owner
|
ELE13-00368
| ELE-Aging Inspection | 9/18/2015 | 9/18/2015 | 9/18/2015 2:22:59 PM | | DONE |
|
|
Still under construction
|
ELE13-00373
| ELE-Aging Inspection | 9/18/2015 | 9/18/2015 | 9/18/2015 2:11:30 PM | | DONE |
|
|
Still under construction
|
ELE13-00338
| ELE-Aging Inspection | 9/18/2015 | 9/18/2015 | 9/18/2015 2:10:37 PM | | DONE |
|
|
Still under construction
|
GCE15-00095
| GCE-Final | 9/18/2015 | 9/18/2015 | 9/18/2015 2:09:00 PM | P | FAIL |
|
|
Lewis ###-#### 110.24- Available fault current shall be posted and date value was calculated. 230.70- Main disconnect shall be identified as to its purpose. 330.30- MC cable shall be secured with in 12" of back exit sign. 406.6- Replace broken receptacle plate west wall. 408.4- Circuit directory shall be completed on new panel. 408.7- Existing panels, unused openings shall be closed.
|
GCE15-00117
| GCE-Final | 9/17/2015 | 9/18/2015 | 9/18/2015 1:30:15 PM | P | PASS |
|
|
Stephanie ###-#### Final ok
|
ELE15-02331
| Final | 9/18/2015 | 9/18/2015 | 9/18/2015 12:32:14 PM | P | FAIL |
|
|
Inspection requested via web by daniel bibikov 300.15- NM cable shall terminate in a box for the receptacle outlet located in net panel.
|
ELE15-02086
| Final | 9/17/2015 | 9/18/2015 | 9/18/2015 11:20:17 AM | A | PASS |
|
|
Kevin Phone #: ###-#### Final ok
|
ELE15-02334
| Final | 9/18/2015 | 9/18/2015 | 9/18/2015 11:19:52 AM | P | FAIL |
|
|
110.26- Works space, minimun of 30" wide and 36" deep shall be maintained for work space for pool panel. 680.21(C)- Outlets supplying pool pump motors shall be provided with GFCI protection. Unable to verify branch circuit feeding pool panel due to no answer at door.
|
ELE15-02984
| Electrical Rough-In | 9/17/2015 | 9/18/2015 | 9/18/2015 10:53:42 AM | A | PASS |
|
|
code 1427 Phone #: ###-#### Inspection requested via web by kendall bender space 13909 wall rough in ok cover
|
ELE15-02926
| Temporary Service | 9/18/2015 | 9/18/2015 | 9/18/2015 10:19:08 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 590.6- All temporary power provided for construction shall have GFCI protection.
|
ELE15-02505
| Final | 9/18/2015 | 9/18/2015 | 9/18/2015 9:55:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Rowdy Monroe Final ok
|
ELE15-01928
| Electrical Rough-In | 9/17/2015 | 9/18/2015 | 9/18/2015 9:29:45 AM | A | PASS |
|
|
wall pack rough in Phone #: ###-#### Inspection requested via web by Scott Campbell 3 additional wall packs west side rough in ok cover
|
ELE15-02988
| Temporary Service | 9/17/2015 | 9/18/2015 | 9/18/2015 9:16:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
|
ELE15-01856
| Final | 9/17/2015 | 9/18/2015 | 9/18/2015 9:01:18 AM | A | PASS |
|
|
Dan garage code-1234 Phone #: ###-#### Inspection requested via web by Dan Hobdey Final ok
|
ELE15-02990
| Temporary Service | 9/18/2015 | 9/18/2015 | 9/18/2015 8:25:15 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Shaun Kirkman t/s u/g n ok
|
ELE15-02545
| Electrical Rough-In | 9/17/2015 | 9/18/2015 | 9/18/2015 8:13:22 AM | A | PASS |
|
|
We are requesting a wall rough-in inspection in the customer service area for Friday 9/18/15 in the AM. Our contact for this is Todd @ ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate Rough in ok cover
|