Inspections for the day of: Monday, September 18, 2017.
Number of inspections: 20
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorEric Strole
TitlePLM/MEC-INSPECTOR
Phone #794-7913
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM17-03550 Final9/18/20179/18/20179/18/2017 3:17:39 PMPCANC
Michael-water softner Phone #: ###-####-Contractor who installed softner needs to pull permit.
PLM17-03185 Plumbing Rough-in9/15/20179/18/20179/18/2017 3:04:19 PMPFAIL
Phone #: ###-#### Inspection requested via web by Brian Johansen-DWV & water test fail.
PLM17-03553 Sprinkler (Final)9/18/20179/18/20179/18/2017 2:48:52 PMPPASS
Genaro Phone #: ###-####
PLM17-03553 DOC - Permit Finaled9/18/20179/18/20179/18/2017 2:48:42 PMPPASS
PLM17-03468 Plumbing Rough-in9/18/20179/18/20179/18/2017 2:28:45 PMPPASS
Call Kevin ###-#### Phone #: ###-#### Inspection requested via web by Kevin Smith
PLM17-03546 Plumbing Rough-in9/18/20179/18/20179/18/2017 2:23:13 PMPFAIL
Phone #: ###-#### Inspection requested via web by Samuel Drake-Need to fix backgraded vent in laundry room. Trap arm for toilet can only be 6'. Need to finish rough-in. Need to replace mission band with no-hub band.
MEC17-03161 Rough-in9/15/20179/18/20179/18/2017 1:42:26 PMPPASS
Field Super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC17-03161 Pressure Test9/15/20179/18/20179/18/2017 1:42:13 PMPCANC
Field Super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC17-02581 Final9/18/20179/18/20179/18/2017 1:21:37 PMPFAIL
Will Phone #: ###-####-Need to provide access to gas valve to fireplace so it is not concealed and has access for operation. Need UV protection on linesets at A/C'c.
PLM17-03525 Final9/18/20179/18/20179/18/2017 12:43:02 PMPNH
Call Donna Woods at ###-#### x 2905 for directions if needed Phone #: ###-#### Inspection requested via web by Mary LaFayette-No access, left notice.
PLM16-03063 Final9/18/20179/18/20179/18/2017 11:25:24 AMAPART
Condos on north side are ready for final inspection Phone #: ###-#### Inspection requested via web by Brent Lacy-All T&P's require an air gap above hub drains.
PLM17-03455 Final9/13/20179/18/20179/18/2017 11:07:20 AMAPASS
Phone #: ###-#### Inspection requested via web by Mary LaFayette
MEC17-04179 Pressure Test9/15/20179/18/20179/18/2017 10:10:47 AMAFAIL
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek-5 lb flue test for furnace fail. 5 lb flue test for w/h pass. 20 lb gas test pass.
MEC17-04179 Rough-in9/15/20179/18/20179/18/2017 10:09:20 AMAPASS
Call Jason with any issues @ 412.6696 Phone #: ###-#### Inspection requested via web by Dawn Kalsbeek
PLM17-00980 Final9/16/20179/18/20179/18/2017 9:50:05 AMAPASS
Garage code 1001 lock button. Phone #: ###-#### Inspection requested via web by David Stephenson
MEC17-04093 Rough-in9/15/20179/18/20179/18/2017 9:01:57 AMAPASS
mechanical fireplace rough in inspection Phone #: ###-#### Inspection requested via web by Dan Otero
PLM17-02690 Final9/15/20179/18/20179/18/2017 8:52:25 AMAPASS
Garage code 1001 lock button. Phone #: ###-#### Inspection requested via web by David Stephenson
PLM17-03468 Plumbing Rough-in9/15/20179/18/20179/18/2017 8:16:10 AMAFAIL
Call Kevin ###-#### Phone #: ###-#### Inspection requested via web by Kevin Smith-Need to fix backgraded vent in wall between back to back baths and missing nailplates.
PLM17-03468 Plumbing Rough-in9/15/20179/18/20179/18/2017 6:21:15 AMACANC
PLM16-02693 PLM-Aging Inspection9/18/20179/18/20179/18/2017 6:18:23 AM PART
No calls