ELE17-03140
| Final | 9/18/2019 | 9/18/2019 | 9/18/2019 4:19:38 PM | P | PASS |
|
|
Duane Oreilly contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce Correction made. Final ok
|
ELE19-02771
| Final | 9/18/2019 | 9/18/2019 | 9/18/2019 2:44:38 PM | P | FAIL |
|
|
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden 210.8(B)- GFCI protection shall be supplied for drinking fountain. Contact stated ordering as we speak. No print on site to reference, south door of warehouse does not have exit or out emergency egress. Contact stated items are not shown on print.
|
ELE19-02772
| Final | 9/18/2019 | 9/18/2019 | 9/18/2019 2:41:43 PM | P | PASS |
|
|
Contact: Mike Mulvahill Phone #: ###-#### Inspection requested via web by Deb Gooden Final ok
|
ELE19-01440
| Final | 9/18/2019 | 9/18/2019 | 9/18/2019 1:52:27 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks 352.46- Where a conduit enters a box, fitting, or enclosure a bushing of adapter shall be provided to protect the wiring from physical damage.
|
ELE18-01935
| Final | 9/17/2019 | 9/18/2019 | 9/18/2019 11:25:29 AM | A | PART |
|
|
Final Inspection for Units 203, 513, 514, and 515. Contact John (Homey) McElroy Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. TCO ok
|
ELE19-03488
| Conference | 9/17/2019 | 9/18/2019 | 9/18/2019 9:57:08 AM | A | DONE |
|
|
Please call Luke to discuss top out of plywood and sheetrock in hallways and general installation nature. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo Discussed the cover of 1 side of walls, (top out) only. BCC 4-05-23 It shall be unlawful to conceal any wiring or equipment prior to having same inspected by City of Boise Electrical inspector. Contact stated no wiring in areas in question so top out OK
|
ELE19-03488
| Electrical Rough-In | 9/18/2019 | 9/18/2019 | 9/18/2019 9:52:19 AM | P | PART |
|
|
Please call Luke to discuss top out of plywood and sheetrock in hallways and general installation nature. Thanks. Phone #: ###-#### Inspection requested via web by Rafael Castillo One side cover on upper portion of walls only rough in ok cover
|
ELE19-02169
| Electrical Rough-In | 9/16/2019 | 9/18/2019 | 9/18/2019 9:33:24 AM | A | PASS |
|
|
Contact: Cindy Wolff, final ceiling inspection please Phone #: ###-#### Inspection requested via web by Deb Gooden Grid complete. Grid rough in ok cover
|