Inspections for the day of: Monday, September 19, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE04-03015 Rough-In Permanent Service9/19/20059/19/20059/19/2005 3:37:58 PMPPART
larry Note: pool grounding ; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles partial bonding pool and conference ok
ELE05-03376 Electrical Rough-In9/19/20059/19/20059/19/2005 2:51:01 PMPFAIL
Scheduled by a contractor via Hello! on 9/19/2005 at 7:47:35 AM. Contact: ###-####. cor. not made still needs to meet 300.4(A)(1)&(D) called
ELE05-03408 Temporary Service9/19/20059/19/20059/19/2005 1:39:40 PMPNR
tom ###-#### -for t/p called no t/s at site
ELE05-02977 Conference9/19/20059/19/20059/19/2005 1:23:50 PMPNH
Scheduled by a contractor via Hello! on 9/19/2005 at 7:16:16 AM. Contact: ###-####. called no response ,stop at job site no electricians there
ELE05-02284 Final9/19/20059/19/20059/19/2005 12:59:44 PMPPASS
darrell; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
ok card signed
ELE05-03405 Electrical Rough-In9/19/20059/19/20059/19/2005 12:28:21 PMPPASS
###-#### - allen r/i ok
ELE05-03023 Final9/16/20059/19/20059/19/2005 10:20:29 AMAPASS
Scheduled by a contractor via Hello! on 9/16/2005 at 3:19:48 PM. Contact: ###-####. ok card signed
ELE05-03374 Rough-In Permanent Service9/16/20059/19/20059/19/2005 9:57:52 AMACANC
joe; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles see added p/s,cor. posted called needs conn. for GEC top of panel, remove sprinkler timer from below panel 110.26 , 440.64(E) provide LCDI,or AFCI on window A/C unit, wire D W
ELE05-03375 Final9/16/20059/19/20059/19/2005 9:04:13 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Dana Moyer cor. posted called 110.26(F) clearence for p/s, BCC no violation retained, 334.12 romex not allowed for o/h drop house to garage, 225.18 clearence
ELE05-03399 Final9/16/20059/19/20059/19/2005 8:30:24 AMAFAIL
Trench Inspection; Phone #: ###-#### Internet Inspection Request from: Dana Moyer cor. posted called spa not listed, needs bonding, and move phone equip that is within 5 ft
ELE05-03374 Permanent Service9/19/20059/19/20059/19/2005 12:00:00 AMAPASS
p/s o/h rec. ok
ELE05-03221 Final9/19/20059/19/20059/19/2005 12:00:00 AMPPASS
ok
ELE05-03405 Permanent Service9/19/20059/19/20059/19/2005 12:00:00 AMPPASS
###-#### - allen p/s u/g new ok