ELE05-02184
| ELE-Aging Inspection | 9/19/2005 | 9/19/2005 | 9/21/2005 2:48:32 PM | | PASS |
|
|
ok final wall sign
|
ELE05-02608
| ELE-Aging Inspection | 9/19/2005 | 9/19/2005 | 9/20/2005 10:01:24 AM | | NR |
|
|
suc called t/w mike
|
ELE05-03413
| Electrical Rough-In | 9/19/2005 | 9/19/2005 | 9/19/2005 4:25:59 PM | P | PASS |
|
|
###-#### - ron ok cover ri
|
ELE05-03393
| Electrical Rough-In | 9/19/2005 | 9/19/2005 | 9/19/2005 3:50:41 PM | P | NR |
|
|
Office remodel.Demo walls. Relocate fluorescent lighting. Thanks; Phone #: ###-#### Internet Inspection Request from: Barry Kendall called did not know what i was to inspect they need to open the area of the ceiling where work was done so i can see it.
|
ELE05-02972
| Electrical Rough-In | 9/19/2005 | 9/19/2005 | 9/19/2005 3:48:57 PM | P | PASS |
|
|
###-#### - zane (duplexes) ok cover ri note one side does not have ufer ground. t/w zane it needs to be 20ft #4 cu with 2 inches concrete cover & inspected
|
ELE05-03415
| Electrical Rough-In | 9/19/2005 | 9/19/2005 | 9/19/2005 3:46:14 PM | P | PART |
|
|
Phone #: ###-#### x39 Internet Inspection Request from: Kristopher wilson ok cover ri walls only & do not cover ceiling it needs to be cleaned up no code violations shall be retained. t/w electrician & general contractor.
|
ELE05-03414
| Final | 9/19/2005 | 9/19/2005 | 9/19/2005 3:43:20 PM | P | PASS |
|
|
###-#### - bob grounding brought up to code all mast raised for clearances in drive & parking lot ok final
|
ELE05-01223
| Final | 9/16/2005 | 9/19/2005 | 9/19/2005 9:02:44 AM | A | PASS |
|
|
blake; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok final
|
ELE05-02955
| Final | 9/17/2005 | 9/19/2005 | 9/19/2005 9:00:50 AM | A | PASS |
|
|
Mike, this is a clean room tool in Fab 4.; Phone #: ###-#### Internet Inspection Request from: Eric Landberg ok final
|
ELE05-02146
| Final | 9/14/2005 | 9/19/2005 | 9/19/2005 9:00:25 AM | A | PASS |
|
|
Final inspection of clean room tool installed in building 3. Internet Inspection Request from: Del Elwood ok final
|
ELE05-03387
| Temporary Service | 9/16/2005 | 9/19/2005 | 9/19/2005 8:40:05 AM | A | PASS |
|
|
###-#### Internet Inspection Request from: Bob Glenn t/s u/g n ok
|
ELE05-03414
| Permanent Service | 9/19/2005 | 9/19/2005 | 9/19/2005 12:00:00 AM | P | PASS |
|
|
###-#### - bob ok p/s o/h reconnect 3 service masts.
|
ELE05-03413
| Permanent Service | 9/19/2005 | 9/19/2005 | 9/19/2005 12:00:00 AM | P | PASS |
|
|
###-#### - p/s u/g n ok
|