Inspections for the day of: Monday, September 19, 2005.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00499 INSP-Conference9/13/20059/19/20059/26/2005 12:03:26 PMPDONE
I left a notice with Judy stating: This permit was failed on 9/22/04. I have followed up twice with the contractor about completing the permit. Once on 8/16/05 and the other on 9/13/05. No action has been taken so far. Owner is being given until October 3, 05 to have permit finaled. If permit is not finaled the hood will be red tagged for shutdown and no cooking will be allowed until the permit has been finaled. A follow up inspection has been scheduled.
FIR05-00515 INSP-Sprinkler Rough-in/Hydro9/19/20059/19/20059/21/2005 7:39:01 AMPPASS
Scheduled by a contractor via Hello! on 9/19/2005 at 10:04:18 AM. Contact: ###-####.
BLD05-01927 FIRE-Final Inspection9/16/20059/19/20059/19/2005 9:54:03 AMAFAIL
Provide fire extinguishers per review comment #7. Provide indicator at the main exit. Provide approved hardware on the west exit doors. Provide fire alarm permit for the connection of the duct smoke detector to the fire alarm panel.
BLD05-01926 FIRE-Final Inspection9/16/20059/19/20059/19/2005 9:51:32 AMPFAIL
Provide fire extinguishers per review comment #7. Provide indicator at the main exit. Provide fire alarm permit for the connection of the duct detector to the fire alarm panel. Per contractor the address has been changed to 2962.
BLD05-01707 FIRE-Final Inspection9/16/20059/19/20059/19/2005 9:49:37 AMAFAIL
Provide twice the amount of fire extinguishers or 4A's. Provide indicator at the main exit. Provide approved hardware on both west exit doors. Per contractor the address has been changed to 2940.
FIR03-00395 INSP-Final Inspection9/16/20059/19/20059/19/2005 9:46:59 AMACANC
Per Alex the power does not shut down upon the activation of the hood suppression system.
FIR03-00405 INSP-Final Inspection9/16/20059/19/20059/19/2005 9:35:20 AMAFAIL
mike; Phone #: ###-####
Electrical did not shut off on the gas/electric hood when the test link was cut. Could not get power to the electric only hood. Need to retest everything.