Inspections for the day of: Tuesday, September 19, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03407 Final9/19/20069/19/20069/19/2006 3:44:52 PMPPASS
phil; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-02603 Final9/15/20069/19/20069/19/2006 3:10:47 PMPPASS
heidi - call prior to insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok
ELE06-03372 Rough-In Permanent Service9/19/20069/19/20069/19/2006 2:22:50 PMPPASS
rough in amd permanent power Internet Inspection Request from: Rowdy Monroe
r/i p/s u/g new ok
ELE06-03372 Electrical Rough-In9/19/20069/19/20069/19/2006 2:22:19 PMPCANC
rough in amd permanent power Internet Inspection Request from: Rowdy Monroe
ELE06-03499 Temporary Service9/19/20069/19/20069/19/2006 1:32:47 PMPPASS
Kathy; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley
t/s u/g new ok
ELE06-03473 Final9/19/20069/19/20069/19/2006 1:06:25 PMPPASS
Work performed by Aaron White.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz ok
ELE06-02943 Permanent Service9/18/20069/19/20069/19/2006 12:21:05 PMPPASS
service change; Phone #: ###-#### Internet Inspection Request from: Therrin Robertson p/s u/g rec. ok
ELE06-03492 Electrical Rough-In9/18/20069/19/20069/19/2006 12:14:22 PMAPASS
Please contact Jim Vincent at ###-#### prior to arrival for access. Remodel of kitchen, nook, and living room.; Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok
ELE06-03495 Electrical Rough-In9/19/20069/19/20069/19/2006 10:49:29 AMAPART
Please call Jason before you get there so he can meet with you. Use number listed. Thank you.; Phone #: ###-#### Internet Inspection Request from: Todd Sellman
walls edward jones
ELE06-03494 Electrical Rough-In9/19/20069/19/20069/19/2006 10:48:56 AMAPART
Please call Jason at the number above before inspection so he can be there to meet with you. Thank you.; Phone #: ###-#### Internet Inspection Request from: Todd Sellman walls banner bank
ELE06-03487 Electrical Rough-In9/18/20069/19/20069/19/2006 9:52:52 AMAFAIL
Work performed by Jim Duffy.; Phone #: ###-#### Internet Inspection Request from: Matt Santacruz corr. called left message, 680.22(A)(3) outlet 10 ft 20 ft from spa, 250.24(A)(5) remove equip grd from neutral bus at subpanel, 220.40 service too small with spa added only 100 A
ELE06-02852 Final9/18/20069/19/20069/19/2006 9:11:13 AMAPASS
contact: Paul Boyer; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok
ELE06-02211 Final9/18/20069/19/20069/19/2006 8:50:28 AMAPASS
Scheduled by a contractor via Hello! on 9/18/2006 at 11:40:09 AM. Contact: ###-####. ok
ELE06-02212 Final9/18/20069/19/20069/19/2006 8:50:12 AMAPASS
Scheduled by a contractor via Hello! on 9/18/2006 at 11:41:26 AM. Contact: ###-####. ok
ELE06-03357 Temporary Service9/18/20069/19/20069/19/2006 8:26:01 AMAFAIL
We have a temporary pole at the Idaho Power box that is ready for inspection for temporary power. Thank you.; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH corr called 250.53 drive grd rod flush, 250.24 terminate GEC to neutral bus, and install bond strap, use plastic conn for GEC