Inspections for the day of: Wednesday, September 19, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01662 Final9/19/20079/19/20079/19/2007 3:58:15 PMPFAIL
paul - please call for access Phone #: ###-#### corr. called 314.16&17 box fill and clamps broken out in cutin box din. nook right side of window, 210.8 all bath recepts shall be gfci protected
ELE07-03222 Electrical Rough-In9/19/20079/19/20079/19/2007 3:07:04 PMPFAIL
All framing is complete. Please call Terry at ###-#### prior to inspection to arrange access. If there are questions please call Steve at ###-#### Phone #: ###-#### Internet Inspection Request from: Steve Craig corr called outlet spacing backsplash kit , wall end of peninsular counter, box fill, kit cutin boxes, 300.4 nail plates, outside boxes shall be flush with combustible material
ELE07-03254 Electrical Rough-In9/19/20079/19/20079/19/2007 2:33:53 PMPPASS
charles Phone #: ###-#### walls ceiling ok
ELE06-04381 Final9/19/20079/19/20079/19/2007 1:59:30 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ok
ELE07-03145 Electrical Rough-In9/19/20079/19/20079/19/2007 1:22:14 PMPCANC
ED @ ###-#### Please call 1/2 hour before going out this is for inspection of the floor heat Phone #: ###-#### called 3 times in the last 11/2 hours no response back
ELE04-00041 Rough-In Permanent Service9/19/20079/19/20079/19/2007 1:20:19 PMPPASS
trevin Phone #: ###-#### r/i u/g and p/s u/g new ok
ELE07-02619 Electrical Rough-In9/18/20079/19/20079/19/2007 10:41:35 AMAPASS
Scheduled by a contractor via Hello! on 9/18/2007 at 4:52:36 PM. Contact: ###-####. all ceilings ok
ELE07-02083 Final9/19/20079/19/20079/19/2007 10:01:23 AMAFAIL
all correction not made and new one created still needs manufacture's info for jtub, panel schedule shall be secific purpose and use, new violation box fill island counter outlet called
ELE07-02611 Electrical Rough-In9/18/20079/19/20079/19/2007 9:35:13 AMAPART
Inspection is for bonding of spa. and electrical work and bonding in pump house Phone #: ###-#### Internet Inspection Request from: JAMES GARCES
spa bond ok no E grid and rump house failed called left message needs grd rods, main breaker and using #8 pool bond as GEC COW
ELE06-04182 Final9/18/20079/19/20079/19/2007 9:07:27 AMAPASS
robert Phone #: ###-#### ok survey needs inuse cover
ELE07-02083 Final9/18/20079/19/20079/19/2007 8:33:51 AMANH
Scheduled by a contractor via Hello! on 9/18/2007 at 9:56:38 PM. Contact: ###-####. called