Inspections for the day of: Wednesday, September 19, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02101 ELE-Aging Inspection9/19/20079/19/20079/21/2007 9:50:44 AM DONE
called contractor about listing label, will call once installed
ELE07-02544 Final9/19/20079/19/20079/19/2007 4:28:46 PMPFAIL
c h Phone #: ###-#### called contr, met builder, left correction notice, nec 400.8 shall not use flexible cord as a substitute for fixed wiring of a structure, 110.3 listing and labelling shall indicate equipment is suitable for installation
ELE07-01473 Final9/19/20079/19/20079/19/2007 4:24:48 PMPPASS
c h Phone #: ###-#### ok to final, no card to sign
ELE07-03113 Final9/19/20079/19/20079/19/2007 2:55:39 PMPPASS
Robin Cox is on site ###-####2 Phone #: ###-#### Internet Inspection Request from: Bryan Atkins ok to final, signed struct card
ELE07-03216 Final9/19/20079/19/20079/19/2007 2:11:59 PMPPASS
Tom Wonacott Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ok to final
ELE07-03216 Permanent Service9/19/20079/19/20079/19/2007 1:51:55 PMPPASS
Tom Wonacott Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called contr, p/s o/h rec ok
ELE07-02288 Electrical Rough-In9/18/20079/19/20079/19/2007 1:27:50 PMPNR
CEILING COVER DAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy seismic wires missing, can lights not installed, raceway not supported, boxes open, will call for later inspection
ELE07-00841 Final9/19/20079/19/20079/19/2007 12:44:04 PMPFAIL
ken Phone #: ###-#### met owner, left corr notice, nec 410.8(D) fluorescent fixture shall be minimum 6" from storage space, 210.12(B) all bedroom outlets shall be protected by afci, 422.31(B) shall provide breaker lock-out for water heater
ELE06-04519 Final9/17/20079/19/20079/19/2007 10:18:55 AMAPASS
this will be for a final inspection. Justin Metcalf will be the contact. Thank you Phone #: ###-#### Internet Inspection Request from: Laura Longshaw signed occ card, ok to final
ELE06-04518 Final9/17/20079/19/20079/19/2007 9:26:13 AMAPASS
This will be for a final. Justin Metcalf wii be the contact. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called elect signed occ card, ok to final
ELE06-04468 Final9/17/20079/19/20079/19/2007 9:10:23 AMAPASS
This will be for a final for this job. Justin Metcalf. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw called elect, signed occ card, ok to final
ELE07-03064 Electrical Rough-In9/18/20079/19/20079/19/2007 8:05:35 AMAPASS
contact jack reinspection for rough-in Phone #: ###-#### Internet Inspection Request from: Emmet Bushman corrections made, ric ok
ELE07-01569 Final9/19/20079/19/20079/19/2007 12:00:00 AMPCANC
garage door jayo-enter Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt