FIR07-00683
| INSP-Final Inspection | 9/19/2007 | 9/19/2007 | 9/20/2007 3:43:52 PM | P | FAIL |
|
|
Missing ceiling tile at several locations, also overdue on a current annual inspection at the existing system riser-last tagged date is 1999.
|
FIR07-00620
| INSP-Sprinkler Rough-in | 9/19/2007 | 9/19/2007 | 9/20/2007 11:37:28 AM | P | CANC |
|
|
Overbooked.
|
BLD07-00328
| FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/20/2007 11:35:58 AM | P | CANC |
|
|
Overbooked.
|
FIR07-00639
| INSP-Final Inspection | 9/18/2007 | 9/19/2007 | 9/20/2007 11:35:18 AM | A | PASS |
|
|
Fire alarm work passed inspection, corrections completed while on site, permit finaled.
|
FIR07-00615
| INSP-Final Inspection | 9/18/2007 | 9/19/2007 | 9/20/2007 11:34:22 AM | A | PASS |
|
|
Fire alarm work passed inspection, corrections made while on site, permit finaled.
|
BLD07-00851
| FIRE-Final Inspection | 9/18/2007 | 9/19/2007 | 9/20/2007 11:33:11 AM | A | FAIL |
|
|
See correction notice for a list of defficient items, also need to final project related fire sprinkler permit prior to life safety final approval.
|
FIR07-00734
| INSP-Final Inspection | 9/18/2007 | 9/19/2007 | 9/20/2007 11:31:16 AM | A | PASS |
|
|
Fire alarm work passed inspection, some required corrections completed while on site, permit finaled.
|
BLD06-00740
| FIRE-Final Inspection | 9/18/2007 | 9/19/2007 | 9/20/2007 11:26:38 AM | A | FAIL |
|
|
See correction notice for list of items in need of repair, also need permit final for the project related fire sprinkler work.
|
BLD06-00500
| FIRE-Final Inspection | 9/18/2007 | 9/19/2007 | 9/20/2007 11:22:54 AM | A | FAIL |
|
|
See eight item correction notice for list of defficiencies, also need to final fire sprinkler permit prior to life safety final approval.
|
FIR07-00222
| FIR-Aging Inspection | 9/19/2007 | 9/19/2007 | 9/20/2007 11:17:37 AM | | DEFR |
|
|
|
FIR07-00718
| INSP-Sprinkler Rough-in | 9/19/2007 | 9/19/2007 | 9/19/2007 2:24:11 PM | P | CANC |
|
|
terry ###-#### Inspection cancelled from web by: John Warnick
|
FIR07-00619
| INSP-Sprinkler Rough-in/Hydro | 9/19/2007 | 9/19/2007 | 9/19/2007 2:24:07 PM | P | CANC |
|
|
Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
|
FIR07-00344
| INSP-Sprinkler Rough-in/Hydro | 9/18/2007 | 9/19/2007 | 9/19/2007 12:20:49 PM | A | PART |
|
|
OH hydrostatic test for the two new dry systems passed, verified resubmitted plans, rough-in is satisfactory, noted missing head guards at some locations, need to provide flexible couplings at the risers, also need to complete 24 hr. pneumatic testing for both systems.
|
FIR06-00995
| INSP-Final Inspection | 9/19/2007 | 9/19/2007 | 9/19/2007 12:00:00 AM | P | CANC |
|
|
mike Phone #: ###-#### rescheduled for tomarrow morning
|
FIR07-00674
| INSP-Final Inspection | 9/17/2007 | 9/19/2007 | 9/18/2007 8:52:55 AM | A | CANC |
|
|
complete fire sprinkler inspection. Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|