Inspections for the day of: Wednesday, September 19, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00683 INSP-Final Inspection9/19/20079/19/20079/20/2007 3:43:52 PMPFAIL
Missing ceiling tile at several locations, also overdue on a current annual inspection at the existing system riser-last tagged date is 1999.
FIR07-00620 INSP-Sprinkler Rough-in9/19/20079/19/20079/20/2007 11:37:28 AMPCANC
Overbooked.
BLD07-00328 FIRE-Final Inspection9/19/20079/19/20079/20/2007 11:35:58 AMPCANC
Overbooked.
FIR07-00639 INSP-Final Inspection9/18/20079/19/20079/20/2007 11:35:18 AMAPASS
Fire alarm work passed inspection, corrections completed while on site, permit finaled.
FIR07-00615 INSP-Final Inspection9/18/20079/19/20079/20/2007 11:34:22 AMAPASS
Fire alarm work passed inspection, corrections made while on site, permit finaled.
BLD07-00851 FIRE-Final Inspection9/18/20079/19/20079/20/2007 11:33:11 AMAFAIL
See correction notice for a list of defficient items, also need to final project related fire sprinkler permit prior to life safety final approval.
FIR07-00734 INSP-Final Inspection9/18/20079/19/20079/20/2007 11:31:16 AMAPASS
Fire alarm work passed inspection, some required corrections completed while on site, permit finaled.
BLD06-00740 FIRE-Final Inspection9/18/20079/19/20079/20/2007 11:26:38 AMAFAIL
See correction notice for list of items in need of repair, also need permit final for the project related fire sprinkler work.
BLD06-00500 FIRE-Final Inspection9/18/20079/19/20079/20/2007 11:22:54 AMAFAIL
See eight item correction notice for list of defficiencies, also need to final fire sprinkler permit prior to life safety final approval.
FIR07-00222 FIR-Aging Inspection9/19/20079/19/20079/20/2007 11:17:37 AM DEFR
FIR07-00718 INSP-Sprinkler Rough-in9/19/20079/19/20079/19/2007 2:24:11 PMPCANC
terry ###-#### Inspection cancelled from web by: John Warnick
FIR07-00619 INSP-Sprinkler Rough-in/Hydro9/19/20079/19/20079/19/2007 2:24:07 PMPCANC
Internet Inspection Request from: John Warnick Inspection cancelled from web by: John Warnick
FIR07-00344 INSP-Sprinkler Rough-in/Hydro9/18/20079/19/20079/19/2007 12:20:49 PMAPART
OH hydrostatic test for the two new dry systems passed, verified resubmitted plans, rough-in is satisfactory, noted missing head guards at some locations, need to provide flexible couplings at the risers, also need to complete 24 hr. pneumatic testing for both systems.
FIR06-00995 INSP-Final Inspection9/19/20079/19/20079/19/2007 12:00:00 AMPCANC
mike Phone #: ###-#### rescheduled for tomarrow morning
FIR07-00674 INSP-Final Inspection9/17/20079/19/20079/18/2007 8:52:55 AMACANC
complete fire sprinkler inspection. Phone #: ###-#### Internet Inspection Request from: Greg Kirkes Inspection cancelled from web by: Greg Kirkes