BLD07-01001
| FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/20/2007 12:57:26 PM | P | PASS |
|
|
Life safety passed.
|
FIR06-00958
| INSP-Final Inspection | 9/17/2007 | 9/19/2007 | 9/19/2007 5:40:23 PM | P | CANC |
|
|
gilbert was not ready for inspection when I was there with Mike and Ken.
|
FIR06-00956
| INSP-Final Inspection | 9/17/2007 | 9/19/2007 | 9/19/2007 5:39:43 PM | P | CANC |
|
|
gilbert was not ready for inspection when I was there with Mike and Ken.
|
FIR06-00811
| INSP-Alarm Testing | 9/18/2007 | 9/19/2007 | 9/19/2007 5:38:13 PM | A | DONE |
|
|
Todays inspection was actually a conference with the fire alarm designer. Mike Timmerman and I went over the a/v and smoke detector deficiencies with him. Mike is allowing him to red line the resubmittals that are waiting in line at the city for review.
|
FIR07-00582
| INSP-Sprinkler Rough-in | 9/18/2007 | 9/19/2007 | 9/19/2007 5:35:17 PM | A | CANC |
|
|
This project not inspected due to contractor wanting to make a determination on obstructions due to issues found at FIR07-00586. It will be rescheduled when a decision is made.
|
FIR07-00585
| INSP-Sprinkler Rough-in | 9/18/2007 | 9/19/2007 | 9/19/2007 5:34:39 PM | A | CANC |
|
|
This project not inspected due to contractor wanting to make a determination on obstructions due to issues found at FIR07-00586. It will be rescheduled when a decision is made.
|
FIR07-00586
| INSP-Sprinkler Rough-in | 9/18/2007 | 9/19/2007 | 9/19/2007 5:32:15 PM | A | PASS |
|
|
There are three items marked on the approved plans that need corrected. The piping is approved for cover and these three items will be checked at the final. I had a conversation with the builder and the sprinkler contractor on potential obstructions. I took them even though I gave the ok to cover if they decided to add sprinkler heads the piping could not be covered until inspected.
|
FIR07-00130
| INSP-Final Inspection | 9/18/2007 | 9/19/2007 | 9/19/2007 2:21:50 PM | A | CANC |
|
|
To be rescheduled per the alarm tech
|
BLD07-01303
| FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/19/2007 2:17:52 PM | P | PASS |
|
|
Life safety passed.
|
BLD07-01646
| FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/19/2007 1:50:49 PM | A | FAIL |
|
|
Provide one additional emerency lighting in construction area.
|
FIR07-00735
| INSP-Sprinkler Rough-in | 9/18/2007 | 9/19/2007 | 9/19/2007 1:28:49 PM | A | PART |
|
|
The overhead piping in the garden area only is ok. The tie with the store system has not been made yet. The four way bracing at the 4" drop down is not done yet. It appears that the hydraulic node points in the calculations are not connected correctly. I contacted Brian about this.
|
FIR07-00791
| INSP-Sprinkler Rough-in | 9/18/2007 | 9/19/2007 | 9/19/2007 1:26:39 PM | A | PASS |
|
|
Permit finaled
|
BLD05-00633
| FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/19/2007 1:25:49 PM | P | CANC |
|
|
Tom, ###-####
|
BLD07-01008
| FIRE-Alarm Testing | 9/18/2007 | 9/19/2007 | 9/19/2007 1:24:51 PM | A | FAIL |
|
|
Provide signage at the area of refuge and provide verification of emergency lighting. The intercom test ok and a active phone has been installed as well.
|
BLD07-01008
| FIRE-Final Inspection | 9/18/2007 | 9/19/2007 | 9/19/2007 1:24:05 PM | A | FAIL |
|
|
Provide signage at the area of refuge and provide verification of emergency lighting. The intercom test ok and a active phone has been installed as well.
|
FIR07-00742
| INSP-Final Inspection | 9/18/2007 | 9/19/2007 | 9/19/2007 9:28:03 AM | A | PASS |
|
|
Hood suppresion system operated correctly.
|
BLD07-02116
| FIRE-Final Inspection | 9/18/2007 | 9/19/2007 | 9/19/2007 9:12:50 AM | A | PASS |
|
|
Life safety pass.
|
FIR07-00336
| INSP-Final Inspection | 9/18/2007 | 9/19/2007 | 9/19/2007 8:28:28 AM | A | CANC |
|
|
Final Inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR07-00756
| INSP-Sprinkler Rough-in/Hydro | 9/18/2007 | 9/19/2007 | 9/19/2007 7:51:40 AM | A | PASS |
|
|
The remaining undergrond supply piping is ok to cover.
|
FIR07-00565
| INSP-Alarm Testing | 9/18/2007 | 9/19/2007 | 9/19/2007 12:00:00 AM | A | CANC |
|
|
rand Phone #: ###-####//cancelled per Sam Rogers pending approval of plan modifications 9/19/07 9:50am
|
BLD07-01819
| FIRE-Final Inspection | 9/19/2007 | 9/19/2007 | 9/19/2007 12:00:00 AM | P | CANC |
|
|
sunny Phone #: ###-####
|
BLD07-01829
| FIRE-Final Inspection | 9/18/2007 | 9/19/2007 | 9/18/2007 11:23:05 AM | P | PASS |
|
|
permit finaled
|