ELE07-00236
| ELE-Aging Inspection | 9/19/2008 | 9/19/2008 | 9/22/2008 3:12:42 PM | | DONE |
|
|
looked at job, locked up, no inspection request yet
|
ELE07-00120
| ELE-Aging Inspection | 9/19/2008 | 9/19/2008 | 9/22/2008 10:28:06 AM | | DONE |
|
|
suc, no call for inspection, no esc this project
|
ELE07-00118
| ELE-Aging Inspection | 9/19/2008 | 9/19/2008 | 9/22/2008 9:56:29 AM | | DONE |
|
|
suc, no call for inspection, no esc this project
|
ELE08-02579
| Permanent Service | 9/19/2008 | 9/19/2008 | 9/19/2008 4:03:24 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton call 30 mins prior ###-#### called contractor, told to check out common lighting, house panel, scope of work, identify meter spaces, no esc this project
|
ESC07-01470
| General Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 3:48:14 PM | P | PART |
|
|
looked ok
|
ESC08-00152
| General Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 3:47:21 PM | P | PART |
|
|
looked ok
|
ESC07-01432
| General Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 3:46:26 PM | P | PART |
|
|
looked ok
|
ESC08-00531
| General Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 3:45:29 PM | A | PART |
|
|
looked ok
|
ESC08-00527
| General Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 3:44:39 PM | A | PART |
|
|
looked ok
|
ESC08-00084
| General Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 3:43:52 PM | A | PART |
|
|
looked ok
|
ELE08-02484
| Electrical Rough-In | 9/18/2008 | 9/19/2008 | 9/19/2008 3:42:50 PM | P | PASS |
|
|
Ready for inspection.SEE KAREN IN SUITE #200,work was done in suite directly above suite #200 Phone #: ###-#### Internet Inspection Request from: gary batten ric ok, no esc this project
|
ELE08-01862
| Electrical Rough-In | 9/19/2008 | 9/19/2008 | 9/19/2008 3:03:32 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Jim Williams walls only ok to cover
|
ELE08-02423
| Electrical Rough-In | 9/19/2008 | 9/19/2008 | 9/19/2008 2:26:31 PM | P | PASS |
|
|
JASON BUILDING 3 L4 UNITS F & E2 Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ric ok 2 units 4th floor anop and log
|
ELE08-02576
| Final | 9/19/2008 | 9/19/2008 | 9/19/2008 1:30:41 PM | P | FAIL |
|
|
Please call Pat Gill, contact ###-#### Phone #: ###-#### Internet Inspection Request from: Debby Ellis called, left correction notice, NEC 250.53(D)(2) shall supplement electrode with one additional electrode, 250.53(G) upper end electrodes shall be flush with or below ground, 110.3(B) shall not use romex connector for abrasion protection unless plastic, 408.4 shall provide circuit directory, BCC shall post job id sticker, shall post address, no esc this project
|
ELE08-02410
| Permanent Service | 9/19/2008 | 9/19/2008 | 9/19/2008 12:34:26 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s u/g n ok
|
ELE08-02557
| Electrical Rough-In | 9/18/2008 | 9/19/2008 | 9/19/2008 10:44:48 AM | A | PASS |
|
|
Inspection for pole light bases and underground conduit. Each pole light will be fused in the handhole. Phone #: ###-#### Internet Inspection Request from: Joe Thomas per 412 and he talked with contractor, no in-line fuses, looked at u/g only for 4 lights, no base inspection except to count 90's, u/g ok to cover only
|
ELE08-02348
| Electrical Rough-In | 9/18/2008 | 9/19/2008 | 9/19/2008 10:28:31 AM | A | PASS |
|
|
basement addition rough in with new sub panel Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contractor, ric basement area ok
|
ELE08-01612
| Final | 9/18/2008 | 9/19/2008 | 9/19/2008 9:55:32 AM | A | PASS |
|
|
milorad Phone #: ###-#### ok to final
|
ELE08-02337
| Final | 9/19/2008 | 9/19/2008 | 9/19/2008 9:23:33 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contractor ok to final, no esc this project
|
ELE08-02575
| Conference | 9/18/2008 | 9/19/2008 | 9/19/2008 9:01:29 AM | A | DONE |
|
|
please call 20 minutes prior to arrival. Phone #: ###-#### Internet Inspection Request from: John Edwards looked at x-ray hook-up for metal piping and wire sizing, no esc this project
|
ELE08-02211
| Temporary Service | 9/19/2008 | 9/19/2008 | 9/19/2008 8:43:03 AM | A | PASS |
|
|
dale Phone #: ###-#### t/s u/g n ok, no esc this project
|
ELE08-01563
| Electrical Rough-In | 9/18/2008 | 9/19/2008 | 9/19/2008 8:20:00 AM | A | PASS |
|
|
JASON Phone #: ###-#### west stairwell only anop ok to cover
|