Inspections for the day of: Friday, September 19, 2008.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00572 INSP-Final Inspection9/17/20089/19/20089/19/2008 4:29:12 PMAPASS
Fire alarm system test passed.Corrections were made per notes on fire alarm plan review. Kr
FIR08-00239 INSP-Sprinkler Rough-in/Hydro9/19/20089/19/20089/19/2008 3:38:27 PMPPART
1st floor correction notice items per last inspection okayed with the exception of plans reflecting actual install, discussed next site visit for rough-in work to date.
FIR08-00388 INSP-Sprinkler Rough-in/Hydro9/18/20089/19/20089/19/2008 2:56:20 PMAPART
OH hydrostatic testing including the wet and antifreeze loop system passed, verified c/n items, noted concealed heads at the restrooms may be obstructed by adjacent surface mounted light fixtures when installed.
BLD08-01101 FIRE-Final Inspection9/19/20089/19/20089/19/2008 2:40:05 PMPFAIL
Cannot perform a life safety until fire sprinkler resubmittals have been approved due to the use of sprinkler flex heads that were not shown on sprinkler plans. KR
FIR07-00827 INSP-Sprinkler Rough-in9/18/20089/19/20089/19/2008 2:37:03 PMACANC
don Phone #: ###-####. Will reschedule for next week. KR
BLD08-00894 FIRE-Final Inspection9/18/20089/19/20089/19/2008 2:35:20 PMPPASS
Fire life safety completed. KR
BLD07-02836 FIRE-Final Inspection9/18/20089/19/20089/19/2008 12:44:02 PMAPASS
Life safety completed acceptable, noted landing at the SW exit to be finished when site work is complete.
BLD07-02837 FIRE-Final Inspection9/18/20089/19/20089/19/2008 12:42:00 PMAPASS
Fire life safety inspection completed satisfactory, noted bollards at the new hydrant to be installed and verified at next site visit for project related building permits next week, hardware at the lion holding area exit okayed per review notes, inspection passed.
FIR08-00319 INSP-Final Inspection9/18/20089/19/20089/19/2008 12:36:25 PMAPASS
As-built plans provided reflecting field modifications accepted, items on correction notice completed, some items finished while on site including added sw at the head box and drain piping at the antifreeze RP. Fire sprinkler permit finaled.
FIR08-00281 INSP-Final Inspection9/19/20089/19/20089/19/2008 12:31:05 PMAPASS
UG fire supply line permit finaled.
FIR08-00590 INSP-Final Inspection9/18/20089/19/20089/19/2008 12:29:13 PMPPASS
The hood suppression system functioned properly under test conditions, inspection passed, permit finaled.
FIR08-00486 INSP-Final Inspection9/18/20089/19/20089/19/2008 12:27:45 PMAPASS
Fire alarm field testing passed, permit finaled.
FIR08-00613 INSP-Alarm Testing9/18/20089/19/20089/19/2008 10:22:51 AMAPART
See red lined notes for areas that were inspected. Also see red lin note for a device that needs to be added in room 134A work room. KR
BLD08-01294 FIRE-Final Inspection9/18/20089/19/20089/19/2008 12:00:00 AMPCANC
conrad Phone #: ###-####