FIR08-00572
| INSP-Final Inspection | 9/17/2008 | 9/19/2008 | 9/19/2008 4:29:12 PM | A | PASS |
|
|
Fire alarm system test passed.Corrections were made per notes on fire alarm plan review. Kr
|
FIR08-00239
| INSP-Sprinkler Rough-in/Hydro | 9/19/2008 | 9/19/2008 | 9/19/2008 3:38:27 PM | P | PART |
|
|
1st floor correction notice items per last inspection okayed with the exception of plans reflecting actual install, discussed next site visit for rough-in work to date.
|
FIR08-00388
| INSP-Sprinkler Rough-in/Hydro | 9/18/2008 | 9/19/2008 | 9/19/2008 2:56:20 PM | A | PART |
|
|
OH hydrostatic testing including the wet and antifreeze loop system passed, verified c/n items, noted concealed heads at the restrooms may be obstructed by adjacent surface mounted light fixtures when installed.
|
BLD08-01101
| FIRE-Final Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 2:40:05 PM | P | FAIL |
|
|
Cannot perform a life safety until fire sprinkler resubmittals have been approved due to the use of sprinkler flex heads that were not shown on sprinkler plans. KR
|
FIR07-00827
| INSP-Sprinkler Rough-in | 9/18/2008 | 9/19/2008 | 9/19/2008 2:37:03 PM | A | CANC |
|
|
don Phone #: ###-####. Will reschedule for next week. KR
|
BLD08-00894
| FIRE-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 2:35:20 PM | P | PASS |
|
|
Fire life safety completed. KR
|
BLD07-02836
| FIRE-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 12:44:02 PM | A | PASS |
|
|
Life safety completed acceptable, noted landing at the SW exit to be finished when site work is complete.
|
BLD07-02837
| FIRE-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 12:42:00 PM | A | PASS |
|
|
Fire life safety inspection completed satisfactory, noted bollards at the new hydrant to be installed and verified at next site visit for project related building permits next week, hardware at the lion holding area exit okayed per review notes, inspection passed.
|
FIR08-00319
| INSP-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 12:36:25 PM | A | PASS |
|
|
As-built plans provided reflecting field modifications accepted, items on correction notice completed, some items finished while on site including added sw at the head box and drain piping at the antifreeze RP. Fire sprinkler permit finaled.
|
FIR08-00281
| INSP-Final Inspection | 9/19/2008 | 9/19/2008 | 9/19/2008 12:31:05 PM | A | PASS |
|
|
UG fire supply line permit finaled.
|
FIR08-00590
| INSP-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 12:29:13 PM | P | PASS |
|
|
The hood suppression system functioned properly under test conditions, inspection passed, permit finaled.
|
FIR08-00486
| INSP-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 12:27:45 PM | A | PASS |
|
|
Fire alarm field testing passed, permit finaled.
|
FIR08-00613
| INSP-Alarm Testing | 9/18/2008 | 9/19/2008 | 9/19/2008 10:22:51 AM | A | PART |
|
|
See red lined notes for areas that were inspected. Also see red lin note for a device that needs to be added in room 134A work room. KR
|
BLD08-01294
| FIRE-Final Inspection | 9/18/2008 | 9/19/2008 | 9/19/2008 12:00:00 AM | P | CANC |
|
|