Inspections for the day of: Monday, September 19, 2011.
Number of inspections: 10
Percentage of inspections complete: 90 %
Percentage of inspections not complete: 10 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ESC11-00466 Aging Inspection9/16/20119/16/2011   
ELE11-01752 Final9/19/20119/19/20119/19/2011 2:29:38 PMPPASS
Robert Phone #: ###-#### corrections made, ok final, signed card
ELE11-01416 Rough-In Permanent Service9/19/20119/19/20119/19/2011 2:25:43 PMPFAIL
Please call Kelly 30mins prior to inspection to meet the inspector on the job site. Phone #: ###-#### >> Inspection requested via web by Kristopher Wilson called, left correction notice, NEC 250.24 shqall provide system grounding, 250.52(A) shall provide electrodes for grounding, 250.56 shall provide 2 electrodes 6' apart, 250.92 shall provide bond bushings, BCC shall provide equipment prior to inspection- service disconnect, shall not cover u/g prior to inspection
ELE07-03492 Electrical Rough-In9/19/20119/19/20119/19/2011 1:34:00 PMPPASS
Greg Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok cover garage ceilings buildings 1 & 3 only
ELE11-01971 Permanent Service9/18/20119/19/20119/19/2011 12:29:44 PMPPASS
>> Inspection requested via web by Terry Scott p/s o/h rec ok
ELE11-01971 Final9/19/20119/19/20119/19/2011 12:29:36 PMPPASS
ok final
ELE08-02423 Final9/16/20119/19/20119/19/2011 10:16:52 AMAPART
Greg Floors 1 B2 & B3 Phone #: ###-#### >> Inspection requested via web by Sean DeLacy buildings 2&3 corridors anop ok final need to see attached rooms
ELE08-02423 Electrical Rough-In9/19/20119/19/20119/19/2011 9:49:19 AMAPASS
ok cover elevator lobby both buidings, P1, elevator control rooms ok
ELE11-02142 Electrical Rough-In9/16/20119/19/20119/19/2011 8:39:42 AMAPASS
Our storage boxes are located behind builing 10A we would like to meet you there and go over the project. Phone #: ###-#### >> Inspection requested via web by Tyler Bowen ri ok for material only for lighting retrofit
ELE09-01705 ELE-Aging Inspection9/19/20119/19/20119/19/2011 7:26:12 AM DONE
still under construction