FIR11-00421
| INSP-Alarm Testing | 9/18/2011 | 9/19/2011 | 9/19/2011 4:53:36 PM | P | PART |
|
|
Items tested today include duct detectors, notification appliances, panel, sprinkler riser supervision, MP, smokes at panels. Items for final include; points map, as-builts for field modifications, lock at breaker, knox box, remove non-functional door mag lock, elevator devices for recall and shunt functions are not installed.
|
BLD11-01471
| FIRE-Final Inspection | 9/19/2011 | 9/19/2011 | 9/19/2011 3:38:10 PM | P | PASS |
|
|
Fire life safety completed acceptable pending one exit sign is relocated per approved plans.
|
FIR11-00439
| INSP-Final Inspection | 9/19/2011 | 9/19/2011 | 9/19/2011 3:36:36 PM | P | PART |
|
|
Verified matched temp. ratings. Final pending two relocated heads and hydrostatic test.
|
BLD11-02176
| FIRE-Final Inspection | 9/16/2011 | 9/19/2011 | 9/19/2011 11:40:25 AM | P | PASS |
|
|
Life safety passed.
|
FIR11-00201
| INSP-Final Inspection | 9/16/2011 | 9/19/2011 | 9/19/2011 11:39:56 AM | A | PASS |
|
|
Fire alarm permit finaled.
|