Inspections for the day of: Monday, September 19, 2011.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00421 INSP-Alarm Testing9/18/20119/19/20119/19/2011 4:53:36 PMPPART
Items tested today include duct detectors, notification appliances, panel, sprinkler riser supervision, MP, smokes at panels. Items for final include; points map, as-builts for field modifications, lock at breaker, knox box, remove non-functional door mag lock, elevator devices for recall and shunt functions are not installed.
BLD11-01471 FIRE-Final Inspection9/19/20119/19/20119/19/2011 3:38:10 PMPPASS
Fire life safety completed acceptable pending one exit sign is relocated per approved plans.
FIR11-00439 INSP-Final Inspection9/19/20119/19/20119/19/2011 3:36:36 PMPPART
Verified matched temp. ratings. Final pending two relocated heads and hydrostatic test.
BLD11-02176 FIRE-Final Inspection9/16/20119/19/20119/19/2011 11:40:25 AMPPASS
Life safety passed.
FIR11-00201 INSP-Final Inspection9/16/20119/19/20119/19/2011 11:39:56 AMAPASS
Fire alarm permit finaled.