Inspections for the day of: Monday, September 19, 2011.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00477 INSP-Final Inspection9/16/20119/19/20119/19/2011 4:19:07 PMAFAIL
All items tested ok except the interconnection of wires run between the buildings. The circuits were not installed in metalic conduit as per the redlined plans, but instead in PVC. After confiring with Doug Poedy it was clear in both NFPA 72 and NEC that the only options for the interbuilding fire alarm circuiting are: provide a metalic cable shield (grounded to the building electrode system), run in metalic conduit (grounded to the building electrode system), or provide isolation modules. Items also needing addressed are the descriptions for the HVAC units in the records storage building.
BLD11-00781 FIRE-Final Inspection9/19/20119/19/20119/19/2011 3:19:47 PMPFAIL
Life safety will be ok to final when the project related fire alarm permit has been passed.
BLD11-00380 FIRE-Final Inspection9/16/20119/19/20119/19/2011 3:19:02 PMAFAIL
Provide lever hardware on the office and kitchen restroom doors, remove the dead bolt from the office door, mount fire extinguishers and remove the palm fronds that are blocking the sidewall sprinkler heads in the seating area.
FIR11-00366 INSP-Final Inspection9/19/20119/19/20119/19/2011 3:17:41 PMPPASS
Permit finaled.
FIR11-00366 INSP-Final Inspection9/19/20119/19/20119/19/2011 3:16:58 PMPPASS
Permit finaled. Forward flush passed
FIR11-00419 INSP-Final Inspection9/19/20119/19/20119/19/2011 3:16:19 PMPPASS
permit finaled
FIR11-00362 INSP-Final Inspection9/19/20119/19/20119/19/2011 3:15:50 PMPPASS
permit finaled
FIR11-00349 INSP-Final Inspection9/19/20119/19/20119/19/2011 3:15:28 PMPPASS
Permit finaled
BLD11-01985 FIRE-Final Inspection9/19/20119/19/20119/19/2011 3:15:02 PMPFAIL
Need the cross access agreement, provide building address, provide fire extinguisher, provide knox box and remove the thumbturn locks.
FIR11-00475 INSP-Final Inspection9/16/20119/19/20119/19/2011 2:33:27 PMAPASS
Permit finaled.
FIR11-00330 INSP-Sprinkler Rough-in/Hydro9/16/20119/19/20119/19/2011 10:56:26 AMAPASS
24 hour air test started at 8:30 am with 43 1/2 psi on the guage.