FIR12-00290
| INSP-Final Inspection | 9/19/2012 | 9/19/2012 | 9/20/2012 4:00:01 PM | P | PASS |
|
|
Fire sprinkler permit finaled. Forward flow completed with two outlets (3"@755/ 2.5"@694).
|
FIR12-00432
| INSP-Sprinkler Rough-in/Hydro | 9/18/2012 | 9/19/2012 | 9/20/2012 12:56:58 PM | P | PASS |
|
|
C/N items finished. Re-inspection passed.
|
FIR12-00525
| INSP-Final Inspection | 9/18/2012 | 9/19/2012 | 9/20/2012 12:54:20 PM | P | PASS |
|
|
Fire alarm work passed functional testing. Permit finaled.
|
FIR12-00412
| INSP-Sprinkler Rough-in | 9/19/2012 | 9/19/2012 | 9/19/2012 5:10:31 PM | P | PART |
|
|
Overhead rough-in including the wet and antifreeze system is approved for cover. Noted two painted pendent heads in need of replacement, discussed construction rating of the riser room with the general contractor.
|
FIR12-00512
| INSP-Sprinkler Rough-in | 9/19/2012 | 9/19/2012 | 9/19/2012 4:50:37 PM | P | PART |
|
|
Overhead fire sprinkler work okay for ceiling cover.
|
FIR12-00384
| INSP-Final Inspection | 9/18/2012 | 9/19/2012 | 9/19/2012 4:48:04 PM | A | PASS |
|
|
Fire sprinkler permit work approved for final status.
|
BLD12-01335
| FIRE-Final Inspection | 9/17/2012 | 9/19/2012 | 9/19/2012 4:47:10 PM | A | FAIL |
|
|
Missing fire sprinkler coverage at the compressor room, SW heads at four locations below overhead doors are in need of adjustment/ replacement due to mechanical damage. Work to be completed by a licensed fire sprinkler contractor under permit provisions.
|