FIR12-00639
| INSP-Sprinkler Rough-in | 9/18/2013 | 9/19/2013 | 9/23/2013 3:42:56 PM | A | NR |
|
|
|
FIR13-00458
| INSP-Sprinkler Rough-in | 9/19/2013 | 9/19/2013 | 9/19/2013 3:55:19 PM | P | PART |
|
|
Overhead work at the grid ceilings approved for cover.
|
FIR13-00432
| INSP-Sprinkler Rough-in | 9/19/2013 | 9/19/2013 | 9/19/2013 3:54:30 PM | P | PART |
|
|
IBR only okayed for cover
|
BLD06-02323
| FIRE-Final Inspection | 9/18/2013 | 9/19/2013 | 9/19/2013 3:53:25 PM | A | PART |
|
|
Building #2 unit #405 passed fire life safety inspection.
|
BLD13-01690
| FIRE-Final Inspection | 9/18/2013 | 9/19/2013 | 9/19/2013 10:29:38 AM | A | NR |
|
|
Noted items include; missing fire extinguishers, need to repair EM lights, provide hardware at the main entry/exit as discussed, reverse hardware at the back excersise room exit door, post max. occupant signage.
|
FIR13-00266
| INSP-Final Inspection | 9/18/2013 | 9/19/2013 | 9/19/2013 10:09:44 AM | A | CANC |
|
|
Need trip test and Final sprinkler system inspection. Please contact Richard Clark ###-#### for questions. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
BLD13-02302
| FIRE-Final Inspection | 9/18/2013 | 9/19/2013 | 9/19/2013 9:48:10 AM | A | PASS |
|
|
Life safety inspection completed acceptable.
|
FIR13-00319
| INSP-Sprinkler Rough-in | 9/18/2013 | 9/19/2013 | 9/19/2013 9:46:52 AM | A | PART |
|
|
Overhead work at the grid ceilings okay for cover. Need as-built plans reflecting actual branchline and main locations. Also need to remove one existing pendent exceeding min. separation from new heads at the workroom.
|