Inspections for the day of: Friday, September 19, 2014.
Number of inspections: 14
Percentage of inspections complete: 93 %
Percentage of inspections not complete: 7 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE14-00152 GCE-Rough-In9/18/20149/18/2014 P 
HP ###-#### underground
ELE12-01815 ELE-Aging Inspection9/19/20149/19/20149/19/2014 2:16:45 PM DONE
business closed and signs removed
ELE12-01815 Final9/19/20149/19/20149/19/2014 2:16:17 PMPPASS
business closed and signs removed
ELE13-01291 Electrical Rough-In9/18/20149/19/20149/19/2014 2:09:39 PMPPASS
Call Brandon for level 4 in soffit rough in. Phone #: ###-#### Inspection requested via web by Tom Betty r/i ceiling under inspiration studio ok to cover
ELE14-01617 Final9/19/20149/19/20149/19/2014 1:29:23 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov final ok
ELE14-02623 Rough-In Permanent Service9/19/20149/19/20149/19/2014 1:02:50 PMPPASS
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren r/i ok p/s u/g n ok
ELE14-01312 Electrical Rough-In9/19/20149/19/20149/19/2014 12:08:33 PMPPASS
inspection of trench from house to garage Phone #: ###-#### Inspection requested via web by steve sellers u.ground trench ok to cover
ELE14-02540 Electrical Rough-In9/18/20149/19/20149/19/2014 11:36:27 AMPPASS
Robert. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok exterior studio areas only
ELE14-00157 Electrical Rough-In9/18/20149/19/20149/19/2014 11:01:42 AMAPASS
trench inspection Johns phone number Phone #: ###-#### Inspection requested via web by Tom Betty u, ground conduits north ok to cover
ELE13-03459 Electrical Rough-In9/18/20149/19/20149/19/2014 10:32:24 AMAFAIL
David// please for access code Phone #: ###-#### 100amp sub main needs to be in lower position of panel. staple NM cable as per 334.30. 11/4' from edge of bored hole to edge of stud 300.4(A)(1). recetacle required so at no point along wall is more than 6 foot 210.52 (A) (1)
ELE14-01805 Final9/19/20149/19/20149/19/2014 9:33:07 AMPPASS
Phone #: ###-#### Inspection requested via web by ron spen cer final ok
ELE14-02598 Electrical Rough-In9/18/20149/19/20149/19/2014 9:10:11 AMAPASS
Paul. Shed. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i rear bldg. ok NOTE: look for thwn conductors in u.g. feed at final
ELE14-02206 Final9/18/20149/19/20149/19/2014 8:55:22 AMAPASS
Inspection requested via web by Rowdy Monroe final ok
GCE14-00151 GCE-Rough-In9/18/20149/19/20149/19/2014 8:15:16 AMACANC
###-#### correction as per Christina no insp. needed at this time as per Ben