Inspections for the day of: Friday, September 19, 2014.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00475 INSP-Sprinkler Rough-in9/19/20149/19/20149/19/2014 3:45:16 PMPPASS
Underground piping is ok to cover
BLD13-02490 FIRE-Final Inspection9/19/20149/19/20149/19/2014 3:26:49 PMPFAIL
There were no city approved plans or fire review documents for the inspection so I spoke to Nick about a possible requirement for fire dept access signage. No actual inspection was performed.
FIR14-00306 INSP-Final Inspection9/18/20149/19/20149/19/2014 3:07:35 PMAPART
See the city as-builts for devices marked "ok" that were tested today. As-builts show duplicate addresses in the elevator machine room that will need to be corrected. One smoke detector in the elevator machine room did not recall the elevator.
BLD14-01322 FIRE-Final Inspection9/18/20149/19/20149/19/2014 2:36:50 PMACANC
Cancel per Dutch @ ###-#### 30
BLD14-01672 FIRE-Final Inspection9/18/20149/19/20149/19/2014 2:35:58 PMPPASS
Life safety passed
FIR14-00354 INSP-Sprinkler Rough-in/Hydro9/19/20149/19/20149/19/2014 2:35:33 PMPPASS
The 24 hour air test on all four dry pipe systems passed.
BLD14-02176 FIRE-Final Inspection9/19/20149/19/20149/19/2014 2:10:14 PMPPASS
Life safety passed
FIR14-00579 INSP-Final Inspection9/19/20149/19/20149/19/2014 1:58:04 PMPPASS
Permit finaled
BLD14-00215 FIRE-Final Inspection9/19/20149/19/20149/19/2014 1:58:02 PMPPASS
Life safety passed
FIR14-00396 INSP-Final Inspection9/19/20149/19/20149/19/2014 1:16:06 PMPPASS
permit finaled
BLD14-01743 FIRE-Final Inspection9/19/20149/19/20149/19/2014 10:28:47 AMPPASS
Life safety passed
FIR14-00666 INSP-Final Inspection9/19/20149/19/20149/19/2014 10:26:29 AMPPASS
Permit finaled
FIR14-00646 INSP-Final Inspection9/18/20149/19/20149/19/2014 10:06:54 AMAPASS
Permit finaled
BLD14-02409 FIRE-Final Inspection9/17/20149/19/20149/19/2014 9:05:50 AMAPASS
Life safety passed per scope of work for temporary use. Exit signs and emergency lights repaired.
FIR14-00406 INSP-Sprinkler Rough-in/Hydro9/19/20149/19/20149/19/2014 12:00:00 AMPPASS
as per Troy Cobbley passed-ok to put in system