Inspections for the day of: Monday, September 19, 2016.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00502 INSP-Sprinkler Rough-in9/19/20169/19/20169/19/2016 3:45:43 PMPPASS
Rough-in passed. Piping can be covered. Not all of the walls have been installed yet so final pendant head spacing can not be verified yet.
FIR16-00441 INSP-Sprinkler Rough-in9/16/20169/19/20169/19/2016 2:11:44 PMPPASS
Rough-in passed. Tenting passed. Piping can be covered. Riser has not been built yet. Need as-builts showing the pipe routing changes. Fitting counts are the same
FIR16-00444 INSP-Sprinkler Rough-in9/16/20169/19/20169/19/2016 2:07:56 PMPCANC
Joseph Danes and I agreed to inspect this when the tenting has been installed.
FIR16-00577 INSP-Final Inspection9/16/20169/19/20169/19/2016 1:33:16 PMPFAIL
Provide as-builts showing the correct communicator (DSC), provide breaker lock and breaker description on the schedule with-in the breaker panel, provide knox key box per review note #13 (Building is a separate fire alarm system from main school).
BLD16-00922 FIRE-Final Inspection9/16/20169/19/20169/19/2016 9:19:00 AMAPASS
Life safety passed
BLD16-01225 FIRE-Final Inspection9/19/20169/19/20169/19/2016 8:38:39 AMPPASS
Life safety passed. Exit discharge light repaired.
BLD16-01225 FIRE-Final Inspection9/16/20169/19/20169/19/2016 8:16:31 AMAFAIL
The north exit discharge light did not operate