Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-04218 Pressure Test9/19/20179/19/20179/19/2017 2:52:05 PMPNH
PRESSURE WITNESS AND FINAL. TABBY JOLLEY WILL BE HOME HER # ###-#### Phone #: ###-#### Inspection requested via web by Andrea Creek - left a notice
MEC17-04125 Pressure Test9/13/20179/19/20179/19/2017 2:51:45 PMPPASS
installer Miguel ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt - 20lb gas
MEC17-02491 Final9/19/20179/19/20179/19/2017 2:20:32 PMPPASS
Call Matt to meet inspector or make sure someone will the there for him. Phone #: ###-#### Inspection requested via web by Manuel Canto
MEC16-05130 Rough-in9/19/20179/19/20179/19/2017 2:01:09 PMPPASS
Request for R/I inspection 4th floor. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 4th floor unit 24 okay
MEC16-05454 Rough-in9/19/20179/19/20179/19/2017 2:00:42 PMPPASS
Request for R/I inspection 4th floor. Please contact Rob ###-#### with any questions or concerns. Phone #: ###-#### Inspection requested via web by Heather Gransbery - 4th floor units 02, 04, 06, 07, 09, 10, 11, 12, 14, 16, 18, 21, 22
MEC16-02300 Mec-Aging Inspection9/19/20179/19/20179/19/2017 1:45:36 PM CANC
MEC17-02100 Final9/18/20179/19/20179/19/2017 11:34:11 AMAFAIL
THANK YOU Phone #: ###-#### Inspection requested via web by Aaron Alandt - Need air balance report on site
MEC17-04147 Rough-in9/18/20179/19/20179/19/2017 10:54:33 AMAPASS
mechanical fireplace rough in inspection Phone #: ###-#### Inspection requested via web by Dan Otero
MEC16-02661 Final9/18/20179/19/20179/19/2017 10:15:40 AMAFAIL
Call Cary for access Phone #: ###-#### Inspection requested via web by David Tully -
1. Condensate needs to be completed on AC-1
2. Need a copy of the generator commisioning report.
3. Make up air damper for pool equipment and storage room is not hooked up.
4. Need to complete the armaflex and UV protection on the 3rd floor roof.
5. AC's on third floor roof not hooked up or running.
6. third floor air balance not complete.
7. Need to complete condensate piping for pool heaters.
8. Gas flex not allowed to penetrate the outside of the dehumidification unit.
9. plumbing vent on roof needs to be 10' away or 3' above fresh air intake.
10. Need preliminary air balance report to verify ventilation in occupied area's