Inspections for the day of: Tuesday, September 2, 2003.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00062 INSP-Final Inspection8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
Hvac units did not shut down upon alarm, provide the NFPA 72 record of completion forms 9/2/2003 10:36:28 AM
BLD02-02471 FIRE-Sprinkler Rough-in8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
No items on the correction notice have been corrected 9/2/2003 10:37:37 AM
BLD02-02471 FIRE-Final Inspection8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
No items on the correction notice have been corrected 9/2/2003 10:38:57 AM
BLD02-02473 FIRE-Final Inspection8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
No items on the correction notice have been corrected 9/2/2003 10:39:03 AM
BLD02-02473 FIRE-Sprinkler Rough-in8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
No items on the correction notice have been corrected 9/2/2003 10:39:08 AM
BLD02-02474 FIRE-Sprinkler Rough-in8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
No items on the correction notice have been corrected 9/2/2003 10:39:47 AM
BLD02-02474 FIRE-Final Inspection8/29/20039/2/20039/2/2003 12:00:00 AMAFAIL
No items on the correction notice have been corrected 9/2/2003 10:39:34 AM
BLD02-00311 FIRE-Conference8/29/20039/2/20039/2/2003 12:00:00 AMADONE
jim ###-#### Went over alarm audibility issues with the engineer. They do have to meet all requirements of the code. The sprinkler contractor can use the 2002 NFPA 13 earthquaking requirements for the installations on this project 9/2/2003 9:45:25 AM
BLD02-00311 FIRE-Conference8/29/20039/2/20039/2/2003 12:00:00 AMADONE
jim ###-#### Went over alarm audibility issues with the engineer. They do have to meet all requirements of the code. The sprinkler contractor can use the 2002 NFPA 13 earthquaking requirements for the installations on this project 9/2/2003 9:45:25 AM
BLD03-00722 FIRE-Final Inspection8/29/20039/2/20039/2/2003 12:00:00 AMPFAIL
Provide emergency shutoff signage in locations per conversation and provide a fire extinguisher in the shelter 9/2/2003 1:43:43 PM
FIR03-00074 INSP-Sprinkler Rough-in/Hydro8/28/20039/2/20039/2/2003 12:00:00 AMPPASS
sprinkler rough-in is ok. Sprinkler piping is OK to cover 9/2/2003 3:51:56 PM
FIR03-00090 INSP-Sprinkler Rough-in/Hydro9/2/20039/2/20039/2/2003 12:00:00 AMPPART
RICK; Phone #: ###-#### Hydro test is OK 9/2/2003 3:46:27 PM
FIR03-00006 INSP-Sprinkler Rough-in/Hydro9/2/20039/2/20039/2/2003 12:00:00 AMPPART
provide as-builts to the city of boise showing the new hose vavle locations, provide EQ bracing on the 4" piping in the locations as discussed, provide signage for the stand pipe per review notes, provide verification that there is adequate clearance for hose hookup at the top north hose vavle with the fire dept. Hydro test is OK 9/2/2003 3:04:21 PM 9/2/2003 3:08:33 PM